General Meter Setup
86
EM13x Series SMART MULTIFUNCTION METER
Table 11: Digital Inputs Options
T
h
e
d
e
b
o
u
n
c
e
t
i
m
e
i
s
a
p
a
The debounce time is applied the same for all digital inputs. If you
change the debounce time for a digital input, the same debounce time
is automatically assigned to the others.
Configuring Relay Outputs
The PM130 PLUS can be provided with one relay (standard) and 2 or 4
optional relay outputs. Each relay can be operated either locally from
the alarm/control setpoints in response to an event or by a remote
command sent through communications. It can also be linked to an
internal pulse source to produce energy pulses.
Using PAS
Select
General Setup
from the
Meter Setup
menu, and then click on
the
Relay Outputs
tab.
Parameter
Options
Default
Description
Input Polarity NORMAL
INVERTING
NORMAL For the normal polarity, the open
to closed transition is considered
closed. For the inverting polarity,
the closed to open transition is
considered a closed
Pulse Input
Mode
PULSE MODE
KYZ MODE
PULSE
MODE
In pulse mode, either leading, or
trailing edge of the input pulse is
recognized as an event. In KYZ
mode, both leading and trailing
edges of the input pulse are
recognized as separate events.
Pulse Polarity NORMAL (N.O.),
INVERTING (N.C.)
NORMAL For the normal polarity, the open
to closed transition is considered
a pulse. For the inverting polarity,
the closed to open transition is
considered a pulse.
It has no meaning in KYZ mode
where both transitions are used.
Debounce
Time
1-100 ms
10 ms
The amount of time while the
state of the digital input should
not change to be recognized as a
new state. Too low debounce time
could produce multiple events on
the input change.