Chapter 6
Device
Control and Upgrading
Resetting Accumulators, Maximum Values and Files
EM13x Series SMART MULTIFUNCTION METER
115
Chapter 6
Device Control and
Upgrading
This section describes operations on the meter you can perform from
the front display or via PAS. To access device control options from PAS,
you should have your meter online.
6.1
Resetting Accumulators, Maximum Values and Files
Using the Front Display
Select the
RESET
entry from the main menu. See
Viewing and
Changing Setup Options
in Chapter 3 for information on configuring
parameters via the front display.
To reset the desired values:
Highlight the middle window by pressing briefly the
SELECT
button.
Select a reset entry by scrolling through the list with the
UP
and
DOWN
arrow buttons.
Press the
SELECT
button briefly to highlight the lower item.
Press and hold the
ENTER
button for 5 seconds.
Release the button.
The
do
entry is replaced with
done
showing the operation is complete.
Table 21 shows the reset options available from the front display.
Table 21: Front Display Reset Options
Display Label
Description
Power Dmd
Clears power maximum demands
V/A Dmd
Clears ampere and volt maximum demands
Min/Max
Clears Min/Max log
Counters
Clears all counters
Counter 1 – Counter 4
Clears counter #1-#4
Diagnostics
Clears device diagnostics
Using PAS
Ensure that the
On-line
button on the PAS toolbar is checked, and
then select
Reset
from the
Monitor menu
.