Appendix A Technical Specifications
EM13x Series SMART MULTIFUNCTION METER
143
Appendix A
Technical Specifications
A.1
Environmental Conditions
Operational ambient temperature limit range: –25
C to +60
C
Specified ambient temperature range: –20
C to +60
C
Long-term damp heat withstand according to IEC 68-2-3 <95% (non-
condensing), +40
C
Transport and storage temperature range: –30
C to +85
C
IEC 60068-2-6, AS 60068-2-6 [18]: Vibration
Frequency range: 10Hz to 150Hz
Vibration time (each axis): 75 min
Sweep rate: 1 oct/min
Max Vibration level:10 m/s
2
(1g), f > 60Hz
IEC 60068-2-27, AS 60068-2-27 [19]: Shock
Shock level: 30 g
Time duration: 18 ms
Shape: Half sine
Number of shocks: 18
A.2
Construction
Case enclosure: Reinforced Polycarbonate
Packaging case: Carton and Stratocell® (Polyethylene Foam) brackets
Labels: Polyester film (UL94-V0)
A.3
Three Phase Power Supply – EM133-SE (Y &
)
Indirect Connection or Direct Connection using HACS
Rated input from 1, 2 or 3 phases: 3 x 120/207-277/480 VAC 50/60Hz
Burden 2VA per phase
Direct Connection
Rated input from 1, 2 or 3 phases: 3 x 120/207-230/400 VAC 50/60Hz
Burden 2VA per phase
Isolation:
Input to ground: 4000V AC
A.4
Auxiliary Power Supply – EM132-133
Rated input: 40-300VAC 50/60Hz, 40-300VDC, Burden 5VA
Frequency range operation 25-400 Hz
Isolation:
Input to ground: 4000V AC