Appendix
B
Standards Compliance
150
EM13x Series SMART MULTIFUNCTION METER
Measurement Specifications
Table 23: Measurement Specifications Parameters
Parameter
Full Scale @
InputRange
Accuracy
Range
%
Reading
%
FS
Conditions
Voltage, V
120VxPT @ 120V
400VxPT @ 690V
0.2
0.2
0.02
0.02
10% to 120%
10% to 115%
0 to 1,150,000 V
Starting voltage
1.5-5.0% FS (selectable)
Voltage, V
(EM133-SE model)
V
L
= 120V,
V
L
= 230V
0.2
0.2
0.02
0.02
10% to 120%
10% to 115%
80 to 1,150,000 V
Starting voltage 80VAC
(w/1phase)
Line current, A
CT
0.2
0.02 For In = 5A
1% to 200% FS
For In = 1A
2% to 200% FS
Starting current 0.1% FS
Line current -
direct
50 A
0.2
0.02 2% to 200% FS
Starting current 0.1% FS
Active power, kW
0.36
PT
CT @ 120V
1.2
PT
CT @ 690V
34.5 @(230V,50A)
0.3
0.02
|PF|
0.5
1
-10,000,000 kW to
+10,000,000 kW
Reactive power,
kvar
0.36
PT
CT@ 120V
1.2
PT
CT @ 690V
34.5 @(230V,50A)
0.3
0.03
|PF|
0.9
1
-10,000,000 kvar to
+10,000,000 kvar
Apparent power,
kVA
0.36
PT
CT @ 120V
1.2
PT
CT @ 690V
34.5 @(230V,50A)
0.3
0.02 |PF|
0.5
1
0 to 10,000,000 kVA
Power factor
1.000
0.2
|PF|
0.5,
I
2% FSI
-0.999 to +1.000
Frequency
50 Hz
60 Hz
25 Hz
400 Hz
0.02
0.02
0.04
0.04
V
L-N
> 25V
15 Hz to 70 Hz
15 Hz to 70 Hz
15 Hz to 70 Hz
320 Hz to 480 Hz
Total Harmonic
Distortion, THD
V(I), %Vf (%If)
999.9
1.5
0.2
THD
1%,
V
10% FSV and
V
L-N
> 25V,
I
10% FSI
0 to 999.9
Total Demand
Distortion, TDD, %
100
1.5
TDD
1%,
I
10% FSI,
V
L-N
> 25V
0 to 100
Active energy
Import & Export
In = 5 and 1 A
Class C as per EN50470-3, Class
0.5S under conditions as per
IEC/AZ 62053-22:2003 at 50/60 Hz
& ANSI C12.20 Ac. Class 0.5
0 to 999,999,999 kWh
Reactive energy
Import & Export
In = 5 and 1 A
Class 0.5S under conditions as per
IEC 62053-22:2003, |PF|
0.9 and
at 50/60 Hz
0 to 999,999,999 kvarh
Apparent energy
In = 5 and 1 A
Class 0.5S under conditions as per
IEC 62053-22:2003 at 50/60 Hz
0 to 999,999,999 kVAh
PT - external potential transformer ratio
CT - primary current rating of the external current transformer
FSV - voltage full scale
FSI - current full scale
Vf - fundamental voltage
If - fundamental current
1
@ 80% to 120% of voltage FS, 1% to 200% of current FS at (In = 5 and 1 A), 2% to 200% of
current FS 50 A and frequency 50/60 Hz