1
In [ALARM OUT1], select “REMOTE”.
Selecting “REMOTE” does not cause the terminal to output an alarm signal automatically even if an
alarm condition is detected.
2
In [POLARITY], select the signal polarity of the alarm output terminal.
NO (Normally Open):
The terminal is normally open and closes when an alarm signal is output.
NC (Normally Closed):
The terminal is normally closed and opens when an alarm signal is output.
3
In [ALARM OUT TIME], select how long you want the terminal to output the alarm signal
and click
SET
.
The terminal will stop outputting the alarm signal when the set alarm output time expires.
2SEC, 5SEC, 10SEC, 15SEC, 30SEC, 45SEC, 1MIN, 2MIN, 3MIN, 4MIN, 5MIN
CC (Stops outputting the alarm signal when the corresponding Remote Alarm button is clicked on the live
screen.)
To configure the ALARM OUT 2 terminal to output an alarm signal when a Remote Alarm
button is clicked, select “REMOTE” in [ALARM OUT2] and specify the output conditions for it
in the same way as for the ALARM OUT1 terminal.
Working with Administrator Configuration Screens 50/71