Design of Mini ECO-i SYSTEM
1. Model Selecting and Capacity Calculator
I
Outdoor unit heating capacity correction coefficient during frosting/defrosting (1 – (2))
* To calculate the heating capacity with consideration for frosting/defrosting operation, multiply the heating capacity
found from the capacity graph by the correction coefficient from the table above.
SPW-CR485GX(H)56
130
120
110
100
90
80
70
60
50
40
15
20
25
( C DB)
SPW-CR365GX(H)56
( C DB)
130
120
110
100
90
80
70
60
50
40
15
20
25
SPW-CR605GX(H)56
130
120
110
100
90
80
70
60
50
40
15
20
25
( C DB)
Outdoor unit heating capacity characteristics
Outdoor air intake temp. ( C DB)
0
–20 –15 –10 –5 0 5 10 15
Outdoor air intake temp. ( C DB)
0
–20 –15 –10 –5 0 5 10 15
Outdoor air intake temp. ( C DB)
0
–20 –15 –10 –5 0 5 10 15
Outdoor intake air
–20
–15
–10
–8
–6
–5
–4
–2
–1
0
1
2
3
4
5
6
temp.
(°C WB RH 85%)
Correction
0.97
0.97
0.97
0.96
0.94
0.91
0.89
0.87
0.87
0.87
0.88
0.89
0.91
0.92
0.95
1.0
coefficient
Capacity r
atio (%)
Capacity r
atio (%)
Capacity r
atio (%)