2
2
- 6
Design of Mini ECO-i SYSTEM
1. Model Selecting and Capacity Calculator
Refer to the graph below for the correction coefficients for Ruc and Ruh.
Indoor unit capacity correction coefficient for Ruc (cooling)
Indoor unit capacity correction coefficient for Ruh (heating)
1.0
0.9
0.8
0.7
0.6
0.5
0.4 0.5 0.6 0.7 0.8 0.9 1.0 1.1 1.2 1.3 1.4 1.5 1.6 1.7 1.8 1.9 2.0
Indoor unit capacity correction coef
ficient
Corrected indoor/outdoor capacity ratio (Ruc or Ruh)
Note:
When Ruc or Ruh is less than or equal to 1.0, the indoor unit capacity correction coefficient for both Ruc and Ruh is 1.0.
5. Graph of capacity correction coefficients
I
Graph of outdoor unit capacity characteristics (1 – (1))
Outdoor unit cooling capacity characteristics
–10
120
22WB
19WB
16WB
100
80
35
38
43
80
90
100
104
(1)
(2)
(1)
(2)
(2) CR605GX(H)56
(1) CR365GX(H)56
CR485GX(H)56
Capacity r
atio (%)
Outdoor air intake temp. (
°
C DB)
06-405 Mini-ECOi_TD2 11/6/06 5:14 PM Page 6