3
3
- 43
Control of Mini ECO-i SYSTEM
4. System Controller
I
How to Start Group Operation
To start group operation
Power
Turn the power supply switch on more than 5 hours before starting operation.
1
Press the SELECT button and select GROUP.
2
Select the ZONE No. including the group to be operated by pressing ZONE button.
3
Select the GROUP No. to be operated by pressing GROUP select buttons
.
4
Press the ON button.
5
Set the operation mode by pressing the MODE button.
6
Set the desired temperature by pressing one of the temperature setting buttons
.
7
Set the desired fan speed by pressing the FAN SPEED button.
8
Set the airflow direction to a specific angle or sweep mode.
9
By pressing
, select your desired setting.
Individual: Controls
with
the
remote controller are possible.
Central 1:
Individual ON/OFF operation with the remote controller is inhibited.
Central 2:
Individual ON/OFF, MODE, and Temp. setting operations with the remote
controller are inhibited.
Central 3:
Individual MODE and Temp. setting operations with the remote controller are
inhibited.
Centr
•
al 4:
Individual MODE operation with the remote controller is inhibited.
Under Central/Individual settings other than listed above, “CENTRAL” is displayed.
AUTO
Operation
Depending on the difference between the temperature setting and the room temperature,
heating and cooling alternate automatically so that a uniform room temperature is maintained.
Stop
Confirming the GROUP No. to be selected, press the OFF button.
The flap setting can be performed only for units that have no remote controllers.
8
9
1
2
5
6
7
3
4
Stop
NOTE
06-405 Mini-ECOi_TD3 11/6/06 6:18 PM Page 43
Summary of Contents for SPW-CR365GX56
Page 5: ...1 1 1 Outline of Mini ECO i SYSTEM Contents 1 OUTLINE OF MINI ECO i SYSTEM 1 Line up 1 2 ...
Page 8: ...1 4 MEMO ...
Page 322: ...4 180 MEMO ...
Page 344: ...5 22 MEMO ...
Page 345: ...200611M DC ...