2
2
- 20
Design of Mini ECO-i SYSTEM
2. System Design
Checking of limit density
Density limit is determined on the basis of the size of a
room using an indoor unit of minimum capacity. For
instance, when an indoor unit is used in a room (floor
area 7.43 m
2
×
ceiling height 2.7 m = room volume
20.06 m
3
), the graph at right shows that the minimum
room volume should be 14.1 m
3
(floor area 5.2 m
2
) for
refrigerant of 4.238 kg. Accordingly, openings such as
louvers are required for this room.
<Determination by calculation>
Overall refrigerant charge amount for the air conditioner: kg
(Minimum room volume for indoor unit: m
3
)
=
4.238 (kg) + 3.5 (kg)
= 0.39 (kg/m
3
)
≥
0.3 (kg/m
3
)
20.06 (m
3
)
Therefore, openings such as louvers are required for
this room.
G
Obtain charge amount for each tubing size
Note that the charge amounts per 1 meter are different for each liquid tubing size.
ø9.52
→
LA + LB + LC + LD
: 65 m
×
0.056 kg/m = 3.64 kg
ø6.35
→
1
+
2
+
3
+
4
+
5
: 23 m
×
0.026 kg/m = 0.598 kg
Total
4.238 kg
Additional refrigerant charge amount is 4.238 kg.
Be sure to check the limit density
for the room in which the indoor
unit is installed.
CAUTION
G
Example of each tubing length
Main tubing
Distribution joint tubing
LA = 40 m
Indoor side
LB = 5 m
1
= 5 m
4
= 6 m
LC = 5 m
2
= 5 m
5
= 5 m
LD = 15 m
3
= 2 m
LN
L1
L2
LC
LB
LA
Mai
n
t
u
be of
un
it
1
s
t bra
n
ch
model 74
model 94
model 124 model 164
model 1
8
4
U
n
it di
s
trib
u
tio
n
t
u
be
1
2
3
n
–1
n
Example:
40
3
5
3
0
25
20
15
10
5
0
10
8
.0
94.5
8
1.0
67.5
54.0
40.5
27.0
1
3
.5
0
10
20
3
0
Total amo
un
t of refri
g
era
n
t
Mi
n
. i
n
door floor area
(whe
n
the ceili
ng
i
s
2.7 m hi
g
h)
m
2
k
g
Ra
ng
e below the
de
ns
ity limit
of 0.
3
k
g
/m
3
(co
un
termea
su
re
s
n
ot
n
eeded)
Ra
ng
e above
the de
ns
ity limit
of 0.
3
k
g
/m
3
(co
un
termea
su
re
s
n
eeded)
m
3
06-405 Mini-ECOi_TD2 11/6/06 5:14 PM Page 20
Summary of Contents for SPW-CR365GX56
Page 5: ...1 1 1 Outline of Mini ECO i SYSTEM Contents 1 OUTLINE OF MINI ECO i SYSTEM 1 Line up 1 2 ...
Page 8: ...1 4 MEMO ...
Page 322: ...4 180 MEMO ...
Page 344: ...5 22 MEMO ...
Page 345: ...200611M DC ...