Mini ECO-i SYSTEM Unit Specifications
1. Outdoor Unit
Unit specifications (C)
MODEL No.
Outdoor Unit
SPW-CR605GXH56
POWER SOURCE
220 - 230 - 240 V / Single-phase / 50 / 60 Hz
PERFORMANCE
Cooling
Heating
Capacity
kW
15.5
17.6
BTU / h
52,900
60,000
Air circulation (Hi)
m
3
/min (cu.ft/min)
100 (3,530)
ELECTRICAL RATINGS
Voltage rating
240
220
230
240
Available voltage range
198 – 264
Running amperes
A
V
V
24.4
23.4
22.4
24.5
23.4
22.5
A
28.0
28.0
28.0
–
–
–
–
–
–
Power input
kW
kW
W/W
4.57
4.57
4.57
5.72
5.72
5.72
4.58
4.58
4.58
Max. power input*
Max. running amperes*
Power factor
COP
%
85
85
85
85
85
85
3.39
3.39
3.39
3.84
3.84
3.84
Max. starting amperes
A
Approx. 1 Approx. 1 Approx. 1 Approx. 1 Approx. 1 Approx. 1
FEATURES
REFRIGERANT TUBING
Controls
Microprocessor
Defrost control
Reverse cycle, microprocessor control
Sensor temp. recall function
Past service warnings recall function
R410A - 3.5
Refrigerant amount at shipment
Service function
Refrigerant control
Electronic expansion valve
Operation sound (Hi)
dB-A
m (ft.)
m (ft.)
kg
68
52
External finish
Power level
Pressure level
Galvanized steel plate with powder paint
Outdoor unit is higher than indoor unit: 50 (164)
Outdoor unit is lower than indoor unit: 40 (131)
Refrigerant tube
outer diameter
Liquid tube mm (in.)
9.52 (3/8)
Gas tube
mm (in.)
19.05 (3/4)
Limit of tubing length
150 (492)
Limit of elevation difference
between the 2 units
Refrigerant tubing kit / Joint kit
Optional
Color (Approximate value)
Munsell 1Y 8.5 / 0.5
DIMENSIONS & WEIGHT
Unit dimensions
Package
dimensions
Unit dimensions
Height
mm (in.)
1230 (48-7/16)
Width
mm (in.)
940 (37)
Depth
mm (in.)
340 (13-13/32)
1331 (52-13/32)
1016 (40)
415 (16-11/32)
Net weight
kg (lbs.)
Shipping weight
kg (lbs.)
Shipping volume
m
3
(cu. ft)
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Rated conditions
Cooling: Indoor air temperature 27
°
C DB / 19
°
C WB; Outdoor air temperature 35
°
C DB
*Full-load conditions at Indoor / Outdoor capacity ratio 100%
Cooling: Indoor air temperature 32
°
C DB / 23
°
C WB; Outdoor air temperature 43
°
C DB / 26
°
C WB
Heating: Indoor air temperature 20
°
C DB; Outdoor air temperature 7
°
C DB / 6
°
C WB
220
230
104 (229)
112 (247)
0.56 (19.8)