3
3
- 12
Control of Mini ECO-i SYSTEM
2. Wireless Remote Controller
I
RCS-TRP80ANG.WL for Ceiling Mounted
(T, LD Type)
2-6. Installing the Receiver Unit
(1) To take off the side panel, open the intake grille and
remove the screw. Then remove the side panel by
moving it toward the front (direction of arrow).
(Fig. 3-7)
(2) Wrap the end of a standard (flat) screwdriver blade
with vinyl tape. Then insert the screwdriver blade into
the groove on the side of the cover below the “O”
mark, and pry open the cover. (Fig. 3-8)
(Take care not to scratch the panel.)
(3) Pass the lead wire through the panel, then install the
receiver unit in the panel hole.
(The projections on the receiver unit engage the
panel holes to attach the unit.)
(4) Fasten the receiver lead wire to the fastener that
holds the louver motor wiring. (Fig. 3-9)
(5) Reattach the side panel.
(6) Route the lead wire from the receiver unit along the
louver motor wiring and other wiring and fasten them
with a fastener. (Fig. 3-10)
* Access the hole at the top of the electrical component
box to draw in the wiring.
G
Do not twist the control wiring with the power wiring
because this may cause malfunction.
G
Install a noise filter or take other appropriate action if
electrical noise disturbs the unit’s power supply cir-
cuit.
* For the wiring and test run procedures, refer to “Wiring
the Receiver Unit” and “Test Run.”
NOTE
Fig. 3-7
Panel
Intake grille
Side panel
Fig. 3-8
Insert into groove on
side below “O” mark.
Vinyl tape
Standard screwdriver
(wrapped with vinyl tape)
Cover
Fig. 3-9
Receiver unit
Clamp
Fig. 3-10
Terminal board
Clamp
Clamp