4
4
- 111
Mini ECO-i SYSTEM Unit Specifications
7. Concealed Duct Type (U Type)
Unit specifications (H)
MODEL No.
Indoor Unit
SPW-UR484GXH56(A/B)
POWER SOURCE
220 - 230 - 240 V / Single-phase / 50 Hz
PERFORMANCE
Cooling
Heating
Capacity
kW
14.0
16.0
BTU / h
47,800
54,600
Air circulation (Hi / Me / Lo)
m
3
/h
1,980 / 1,800 / 1,500
Moisture removal (High)
78(8.0): At shipment 113(11.5): Using the booster cable
External static pressure (High)
Pa (mmAq)
Liters/h
6.6
–
ELECTRICAL RATINGS
Voltage rating
240
220
230
240
Available voltage range
198 – 264
198 – 264
Running amperes
A
V
V
1.42
1.43
1.44
1.36
1.37
1.38
Power input
W
308
325
341
296
313
329
Power factor
%
99
99
99
99
99
99
Max. starting amperes
A
2
2
2
2
2
2
FEATURES
Controls
Microprocessor
Timer
ON / OFF Timer (Max. 72 hr)
Fan speeds
3 and Automatic control
Air filter
Field supply
Refrigerant control
Electronic expansion valve
Operation sound (Hi / Me / Lo)
dB-A
40 / 37 / 33
Using the booster cable (Hi / Me / Lo)
dB-A
44 / 40 / 37
Refrigerant tubing connections
Flare type
Refrigerant tube diameter
Liquid tube mm (in.)
9.52 (3/8)
Gas tube
mm (in.)
15.88 (5/8)
Drain connection
25A, OD32 mm
Drain pump
Max. head 50 cm above drain connection
Remote controller
Optional (RCS-SH80AG)
Refrigerant tubing kit / Accessories
Optional / Booster cable
–
Color (Approximate value)
DIMENSIONS & WEIGHT
Package dimensions
Unit dimensions
Unit dimensions
Height
mm (in.)
310 (12-7/32)
358 (14-3/32)
1671 (65-25/32)
783 (30-26/32)
0.468 (16.5)
Width
mm (in.)
1480 (58-9/32)
Depth
mm (in.)
630 (24-26/32)
Net weight
kg (lbs.)
Shipping weight
kg (lbs.)
Shipping volume
m
3
(cu. ft)
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Rated conditions
Cooling: Indoor air temperature 27
°
C DB / 19
°
C WB; Outdoor air temperature 35
°
C DB
Heating: Indoor air temperature 20
°
C DB; Outdoor air temperature 7
°
C DB / 6
°
C WB
220
230
47 (104)
52 (115)
06-405 Mini-ECOi_TD4 11/8/06 4:28 PM Page 111
Summary of Contents for SPW-CR365GX56
Page 5: ...1 1 1 Outline of Mini ECO i SYSTEM Contents 1 OUTLINE OF MINI ECO i SYSTEM 1 Line up 1 2 ...
Page 8: ...1 4 MEMO ...
Page 322: ...4 180 MEMO ...
Page 344: ...5 22 MEMO ...
Page 345: ...200611M DC ...