4
4
- 89
Mini ECO-i SYSTEM Unit Specifications
6. Ceiling-Mounted Type (T Type)
6-1. Specifications
Unit specifications (A)
MODEL No.
Indoor Unit
SPW-TDR124GXH56(A/B)
POWER SOURCE
220 - 230 - 240 V / Single-phase / 50 Hz / 60 Hz
PERFORMANCE
Cooling
Heating
Capacity
kW
3.6
4.2
BTU / h
12,000
14,000
Air circulation (Hi / Me / Lo)
m
3
/h
720 / 600 / 540
Moisture removal (High)
Liters/h
1.4
–
ELECTRICAL RATINGS
Voltage rating
240
220
230
240
Available voltage range
198 – 264
198 – 264
Running amperes
A
V
V
0.26
0.24
0.23
0.26
0.24
0.23
Power input
W
28
29
39
28
28
29
Power factor
%
49
53
53
49
51
53
Max. starting amperes
A
2
2
2
2
2
2
FEATURES
Controls
Microprocessor
Timer
ON / OFF Timer (Max. 72 hr)
Fan speeds
3 and Automatic control
Air filter
Washable, easy access, long life (2,500 hr)
Refrigerant control
Electronic expansion valve
Operation sound (Hi / Me / Lo)
dB-A
35 / 32 / 30
Refrigerant tubing connections
Flare type
Refrigerant tube diameter
Liquid tube mm (in.)
6.35 (1/4)
Gas tube
mm (in.)
12.7 (1/2)
Drain connection
20A, OD26 mm
Remote controller
Optional (RCS-TRP80ANG.WL)
Refrigerant tubing kit / Accessories
Optional / –
Color (Approximate value)
Munsell 10Y 9.0 / 0.4, RAL 9010-GL
DIMENSIONS & WEIGHT
Package dimensions
Unit dimensions
Unit dimensions
Height
mm (in.)
210 (8-9/32)
280 (11-1/32)
958 (38-25/32)
780 (30-23/32)
0.215 (7.6)
Width
mm (in.)
910 (35-26/32)
Depth
mm (in.)
680 (26-25/32)
Net weight
kg (lbs.)
Shipping weight
kg (lbs.)
Shipping volume
m
3
(cu. ft)
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Rated conditions
Cooling: Indoor air temperature 27
°
C DB / 19
°
C WB; Outdoor air temperature 35
°
C DB
Heating: Indoor air temperature 20
°
C DB; Outdoor air temperature 7
°
C DB / 6
°
C WB
220
230
21 (46)