3
3
- 25
Control of Mini ECO-i SYSTEM
2. Wireless Remote Controller
2-23. Test Run Setting
1. Remove the receiver unit face plate, and set the
DIP switch to “Test Run - ON” position.
2. Run the air conditioner using the wireless remote
controller by pressing the “ON/OFF” button.
G
All LEDs (“RUN,” “TIMER” and “STANDBY”) blink
during test run operation.
G
No temperature control is effective with the wire-
less remote controller in the “Test Run – ON” posi-
tion.
To avoid mechanical strain on the air conditioner,
do not use this mode except for conducting a test
run.
3. Select any one of the operation modes HEAT,
COOL or FAN for the test run.
* The outdoor unit will not start running for about 3
minutes after the power ON button is pressed.
4. After the test run operation, stop the air condition-
er using the wireless remote controller, and then
reset the DIP switch in the receiver unit as it was
before. (To prevent constant test running of the air
conditioner, the receiver unit has a 60-minute off-
timer function.)
06-405 Mini-ECOi_TD3 11/6/06 6:18 PM Page 25