4
4
- 4
Mini ECO-i SYSTEM Unit Specifications
1. Outdoor Unit
Unit specifications (B)
MODEL No.
Outdoor Unit
SPW-CR485GXH56
POWER SOURCE
220 - 230 - 240 V / Single-phase / 50 / 60 Hz
PERFORMANCE
Cooling
Heating
Capacity
kW
14.0
16.0
BTU / h
47,800
54,600
Air circulation (Hi)
m
3
/min (cu.ft/min)
100 (3,530)
ELECTRICAL RATINGS
Voltage rating
240
220
230
240
Available voltage range
198 – 264
Running amperes
A
V
V
20.5
19.6
18.8
20.8
19.9
19.1
–
–
–
–
–
–
Power input
kW
kW
W/W
3.83
3.83
3.83
4.90
4.90
4.90
3.90
3.90
3.90
Max. power input*
Power factor
COP
%
85
85
85
85
85
85
3.66
3.66
3.66
4.10
4.10
4.10
Max. starting amperes
A
Approx. 1 Approx. 1 Approx. 1 Approx. 1 Approx. 1 Approx. 1
FEATURES
REFRIGERANT TUBING
Controls
Microprocessor
Defrost control
Reverse cycle, microprocessor control
Sensor temp. recall function
Past service warnings recall function
R410A - 3.5
Refrigerant amount at shipment
Service function
Refrigerant control
Electronic expansion valve
Operation sound (Hi)
dB-A
m (ft.)
m (ft.)
kg
67
51
External finish
Power level
Pressure level
Galvanized steel plate with powder paint
Outdoor unit is higher than indoor unit: 50 (164)
Outdoor unit is lower than indoor unit: 40 (131)
Refrigerant tube
outer diameter
Liquid tube mm (in.)
9.52 (3/8)
Gas tube
mm (in.)
15.88 (5/8)
Limit of tubing length
150 (492)
Limit of elevation difference
between the 2 units
Refrigerant tubing kit / Joint kit
Optional
Color (Approximate value)
Munsell 1Y 8.5 / 0.5
DIMENSIONS & WEIGHT
Unit dimensions
Package
dimensions
Unit dimensions
Height
mm (in.)
1230 (48-7/16)
Width
mm (in.)
940 (37)
Depth
mm (in.)
340 (13-13/32)
1331 (52-13/32)
1016 (40)
415 (16-11/32)
Net weight
kg (lbs.)
Shipping weight
kg (lbs.)
Shipping volume
m
3
(cu. ft)
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Rated conditions
Cooling: Indoor air temperature 27
°
C DB / 19
°
C WB; Outdoor air temperature 35
°
C DB
*Full-load conditions at Indoor / Outdoor capacity ratio 100%
Cooling: Indoor air temperature 32
°
C DB / 23
°
C WB; Outdoor air temperature 43
°
C DB / 26
°
C WB
Heating: Indoor air temperature 20
°
C DB; Outdoor air temperature 7
°
C DB / 6
°
C WB
220
230
104 (229)
112 (247)
0.56 (19.8)
06-405 Mini-ECOi_TD4 11/8/06 4:28 PM Page 4
Summary of Contents for SPW-CR365GX56
Page 5: ...1 1 1 Outline of Mini ECO i SYSTEM Contents 1 OUTLINE OF MINI ECO i SYSTEM 1 Line up 1 2 ...
Page 8: ...1 4 MEMO ...
Page 322: ...4 180 MEMO ...
Page 344: ...5 22 MEMO ...
Page 345: ...200611M DC ...