Design of 3-WAY ECO-i SYSTEM
1
2
3
4
5
6
7
8
4. Installation Instructions
4-1. Indoor Unit
AVOID:
Areas where leakage of flammable gas may be expected.
Places where large amounts of oil mist exist.
Direct sunlight.
Locations near heat sources which may affect the per-
formance of the unit.
Locations where external air may enter the room directly.
This may cause “sweating” on the air discharge ports,
causing them to spray or drip.
Locations where the remote controller will be splashed
with water or affected by dampness or humidity.
Installing the remote controller behind curtains or furniture.
Locations where high-frequency emissions are generated.
Places where blocks air passages.
Places where the false ceiling is not noticeably on an
incline.
DO:
Select an appropriate position from which every corner of
the room can be uniformly cooled.
Select a location where the ceiling is strong enough to
support the weight of the unit.
Select a location where tubing and drain pipe have the
shortest run to the outdoor unit.
Allow room for operation and maintenance as well as un-
restricted air flow around the unit.
Install the unit within the maximum elevation difference
above or below the outdoor unit and within a total tubing
length (L) from the outdoor unit as detailed in Table 1-1.
Allow room for mounting the remote controller about 1 m
off the floor, in an area that is not in direct sunlight nor in
the flow of cool air from the indoor unit. Air delivery will
be degraded if the distance from the floor to the ceiling is
greater than 3 m (for L type, greater than 3.5 m).
Places where optimum air distribution can be ensured.
Places where sufficient clearance for maintenance and
service can be ensured. (Refer to the diagram.)
Concealed-Duct Type
4-Way Semi-Concealed Type
2-Way,
Wall-Mounted Type
Min.15 cm
Front View
15 cm
15 cm
Floor-Standing, Concealed Floor-Standing Type
Min.
10 cm
Min. 100 cm
Min.
10 cm
Min. 100 cm
Horizontal view
Vertical view
Ceiling-Mounted Type
Side view
Min.
n. 25 cm
Min.
n
.
50 cm
Air intake
Air
discharge
Min.
n. 25 cm
Ceiling
Wall
Front view
Max. 25 cm
Obstacle
20
cm
20
cm
100
cm
20
cm
100
cm
Min. 5 cm
Min. 5 cm
Min.
1 m
Air
intake
Air
discharge
Obstacle
Ceiling
Wall
Wall
Side view
Semi-Concealed Type
Semi-Concealed Slim Type
1-Way Semi-Concealed & Slim Type
*
Min.
*
Min.
*
SPW-K075/095/125XH : Min. 5 cm
1 m
1 m
1 m
1 m
1 m
25 cm
25 cm
25 cm
NOTE
The rear of the indoor unit can be installed flush against the
wall.
NOTE
Air delivery will be degraded if the distance from the floor to
the ceiling is greater than 3 m (for L type, greater than 3.5 m).
Fig. 4-1
Fig. 4-2
Fig. 4-3
Fig. 4-5
Fig. 4-4
TD831143-00_W-3WAY.indb 30
2008/12/05 9:40:16
Summary of Contents for SPW-C0705DZH8
Page 2: ...i ...
Page 3: ...ii ...
Page 52: ...2 42 MEMO ...
Page 158: ...3 106 MEMO ...
Page 528: ...4 370 MEMO ...
Page 562: ...6 18 Electrical Data 1 2 3 4 5 6 7 8 2 Indoor Unit Schematic Diagram SPW KR254GXH56 A B ...
Page 575: ...6 31 Electrical Data 1 2 3 4 5 6 7 8 2 Indoor Unit Schematic Diagram SPW DR254GXH56 A B ...
Page 577: ...6 33 Electrical Data 1 2 3 4 5 6 7 8 2 Indoor Unit Schematic Diagram SPW DR364GXH56 A B ...
Page 579: ...6 35 Electrical Data 1 2 3 4 5 6 7 8 2 Indoor Unit Schematic Diagram SPW DR484GXH56 A B ...
Page 581: ...6 37 Electrical Data 1 2 3 4 5 6 7 8 2 Indoor Unit Schematic Diagram SPW DR764GXH56 A B ...
Page 583: ...6 39 Electrical Data 1 2 3 4 5 6 7 8 2 Indoor Unit Schematic Diagram SPW DR964GXH56 A B ...
Page 589: ...6 45 Electrical Data 1 2 3 4 5 6 7 8 2 Indoor Unit Schematic Diagram SPW GU055 075 105XH ...
Page 590: ...6 46 MEMO ...
Page 702: ...8 96 MEMO ...
Page 703: ...SANYO Electric Co Ltd Printed in Japan 200812B DC ...