System Limitations
3
135 kW (48 hp)
40
*1
1:
2:
3:
The outdoor connection main tubing (LO portion) is determined by the total capacity of the outdoor units that
are connected to the tube ends.
If the longest tubing length (L1) exceeds 90 m (equivalent length), increase the sizes of the main tubes (LM) by
1 rank for the discharge tubes, suction tubes, and narrow tubes. (field supplied)
If the longest main tube length (LM) exceeds 50 m, increase the main tube size at the portion before 50 m by 1
rank for the suction tubes and discharge tubes. (field supplied)
(For the portion that exceeds 50 m, set based on the main tube sizes (LA) listed in the table on the following
page.)
Refrigerant Charge Amount at Shipment (for outdoor unit)
SPW-C0705DZH8
SPW-C0905DZH8
SPW-C1155DZH8
SPW-C1305DZH8
SPW-C1405DZH8
Additional Refrigerant Charge
Max. No. allowable connected outdoor units
Max. capacity allowable connected outdoor units
Max. connectable indoor units
Max. allowable indoor/outdoor capacity ratio
50 – 130 %
NOTE
*1: In the case of 22 hp (type 2205) or smaller units, the number is limited by the total capacity of the connected
indoor units.
Additional refrigerant charge amount is calculated from the liquid tubing total length as follows.
*Always charge accurately using a scale for weighing.
Liquid tubing size
6.35
9.52
12.7 15.88 19.05 22.22
Amount of additional
refrigerant charge/m (g/m)
26
56
128
185
259
366
SPW-C0705DZH8
SPW-C0905DZH8
SPW-C1155DZH8
SPW-C1305DZH8
SPW-CR1405DZH8
3.2 kg
3.2 kg
Required amount of additional refrigerant charge = [ (Amount of additional refrigerant charge per meter of each size of liquid
tube × its tube length) + (...) + (...)] + [(Necessary amount of additional refrigerant charge per outdoor unit + (...) + (...)]
Amount of Additional Refrigerant Charge Per Meter, According to Liquid Tubing Size
Necessary Amount of Additional Refrigerant Charge Per Outdoor Unit
2-5
Design of 3-WAY ECO-i SYSTEM
1
2
3
4
5
6
7
8
1. Model Selecting and Capacity Calculator
TD831143-00_W-3WAY.indb 5
2008/12/05 9:40:00
Summary of Contents for SPW-C0705DZH8
Page 2: ...i ...
Page 3: ...ii ...
Page 52: ...2 42 MEMO ...
Page 158: ...3 106 MEMO ...
Page 528: ...4 370 MEMO ...
Page 562: ...6 18 Electrical Data 1 2 3 4 5 6 7 8 2 Indoor Unit Schematic Diagram SPW KR254GXH56 A B ...
Page 575: ...6 31 Electrical Data 1 2 3 4 5 6 7 8 2 Indoor Unit Schematic Diagram SPW DR254GXH56 A B ...
Page 577: ...6 33 Electrical Data 1 2 3 4 5 6 7 8 2 Indoor Unit Schematic Diagram SPW DR364GXH56 A B ...
Page 579: ...6 35 Electrical Data 1 2 3 4 5 6 7 8 2 Indoor Unit Schematic Diagram SPW DR484GXH56 A B ...
Page 581: ...6 37 Electrical Data 1 2 3 4 5 6 7 8 2 Indoor Unit Schematic Diagram SPW DR764GXH56 A B ...
Page 583: ...6 39 Electrical Data 1 2 3 4 5 6 7 8 2 Indoor Unit Schematic Diagram SPW DR964GXH56 A B ...
Page 589: ...6 45 Electrical Data 1 2 3 4 5 6 7 8 2 Indoor Unit Schematic Diagram SPW GU055 075 105XH ...
Page 590: ...6 46 MEMO ...
Page 702: ...8 96 MEMO ...
Page 703: ...SANYO Electric Co Ltd Printed in Japan 200812B DC ...