Liquid tube
diameter
(A)
per 1 m (kg/m) (B)
(A) × (B) kg
La
ø12.7
2
0.128
0.256
Lb
ø12.7
1
0.128
0.128
Lc
ø9.52
1
0.056
0.056
LP
ø15.88
20
0.185
3.700
LA
ø19.05
5
0.259
1.295
LB
ø15.88
6
0.185
1.110
LC
ø12.7
6
0.128
0.768
LD
ø12.7
0.4
0.128
0.051
LE1
ø9.52
5
0.056
0.280
LN
ø15.88
3
0.185
0.555
LG
ø12.7
3
0.128
0.384
LH
ø9.52
4
0.056
0.224
LI
ø9.52
5
0.056
0.280
LJ
ø9.52
5
0.056
0.280
LK
ø12.7
2
0.128
0.256
LL
ø9.52
3
0.056
0.168
LM
ø9.52
4
0.056
0.224
L1
ø9.52
3
0.056
0.168
L2
ø6.35
3
0.026
0.078
L3
ø6.35
3
0.026
0.078
L7
ø9.52
3
0.056
0.168
L8
ø9.52
3
0.056
0.168
L9
ø9.52
4
0.056
0.224
L10
ø6.35
4
0.026
0.104
L11
ø6.35
6
0.026
0.156
L12
ø9.52
4
0.056
0.224
L13
ø9.52
4
0.056
0.224
L14
ø9.52
4
0.056
0.224
L15
ø6.35
6
0.026
0.156
11.987
11.99 kg
Liquid tube
diameter
(A)
per 1 m (kg/m) (B)
(A) × (B) kg
LE2
ø9.52
4
0.056
0.224
LF
ø9.52
5
0.056
0.280
L4
ø9.52
4
0.056
0.224
L5
ø9.52
6
0.056
0.336
L6
ø9.52
7
0.056
0.392
1.4560
1.46 kg
Additional refrigerant charge before extension
Tubing length (m)
Additional refrigerant charge
Total (kg)
Additional refrigerant charge after extension
Tubing length (m)
Additional refrigerant charge
Total (kg)
Calculation of additional refrigerant charge for the entire 3-WAY ECO-i system
(Additional refrigerant charge for entire 3-WAY ECO-i system)
= (Refrigerant charge at outdoor unit)
+ (Necessary amount of additional refrigerant charge per outdoor unit)
+ [Additional total refrigerant charge (before ext after extension) ]
[Before extension : (11.8 + 11.8) + (0 + 3.2) + 11.99 = 38.79 kg ]
= [(11.8 + 11.8 + 11.8) refrigerant charge at outdoor unit]
+ [(0 + 0 + 3.2) necessary amount of additional refrigerant charge per outdoor unit]
+ [(11.99+1.46) additional total refrigerant charge]
= 52.05 (after extension)
2-21
Design of 3-WAY ECO-i SYSTEM
1
2
3
4
5
6
7
8
2. System Design
TD831143-00̲W-3WAY.indb 21
TD831143-00̲W-3WAY.indb 21
2008/12/01 16:15:44
2008/12/01 16:15:44
Summary of Contents for SPW-C0705DZH8
Page 2: ...i ...
Page 3: ...ii ...
Page 52: ...2 42 MEMO ...
Page 158: ...3 106 MEMO ...
Page 528: ...4 370 MEMO ...
Page 562: ...6 18 Electrical Data 1 2 3 4 5 6 7 8 2 Indoor Unit Schematic Diagram SPW KR254GXH56 A B ...
Page 575: ...6 31 Electrical Data 1 2 3 4 5 6 7 8 2 Indoor Unit Schematic Diagram SPW DR254GXH56 A B ...
Page 577: ...6 33 Electrical Data 1 2 3 4 5 6 7 8 2 Indoor Unit Schematic Diagram SPW DR364GXH56 A B ...
Page 579: ...6 35 Electrical Data 1 2 3 4 5 6 7 8 2 Indoor Unit Schematic Diagram SPW DR484GXH56 A B ...
Page 581: ...6 37 Electrical Data 1 2 3 4 5 6 7 8 2 Indoor Unit Schematic Diagram SPW DR764GXH56 A B ...
Page 583: ...6 39 Electrical Data 1 2 3 4 5 6 7 8 2 Indoor Unit Schematic Diagram SPW DR964GXH56 A B ...
Page 589: ...6 45 Electrical Data 1 2 3 4 5 6 7 8 2 Indoor Unit Schematic Diagram SPW GU055 075 105XH ...
Page 590: ...6 46 MEMO ...
Page 702: ...8 96 MEMO ...
Page 703: ...SANYO Electric Co Ltd Printed in Japan 200812B DC ...