5-3
Test Run
1
2
3
4
5
6
7
8
Fig. 5-3
2. Test Run Procedure
Items to Check Before the Test Run
1.
Turn the remote power switch on at least 5
hours before the test, in order to energize
the crank case heater.
2.
Turn the outdoor service valves (4 locations)
to the full-open positions.
Use caution when making the settings. If
there are duplicated system addresses,
or if the settings for the Nos. of the indoor
units are not consistent, an alarm will
occur and the system will not start.
These settings are not made on the
indoor unit PCB.
*1 The unit with the unit No. set to 1 is the
main unit. All other units are sub units.
Recheck the items to check before the test run.
YES
Have the outdoor sub units
been connected?
NO
Set the unit address.
Set the No. of outdoor units.
Set the No. of indoor units.
Are the inter-unit control wires
connected to more than 1 refrigerant
system?
Set the system address.
When multiple outdoor main units exist, disconnect the terminals extended
from the shorted plugs (CN003) at all outdoor main unit PCBs except for 1.
Alternatively, move the sockets to the OPEN side.
<Outdoor unit control PCB>
Unit No. setting switch
(S004 and S005)
(Check the link wiring.)
<Outdoor unit control PCB>
Unit No. setting switch
(S002 and S003)
NO
YES
YES
NO
NO
YES
CASE 1
CASE 2
Refer to Fig. 5-4
Is it possible to turn ON the
power only for the 1 refrigerant system where the
test run will be performed?
Will automatic address setting
be performed in Heating mode?
CASE 3B
CASE 3A
Turn ON the indoor and
outdoor unit power for that
refrigerant system only.
Short-circuit the automatic address pin
(CN100) on the outdoor main unit PCB
for 1 second or longer, then release it.
LED 1 and 2 blink alternately
(about 2 or 3 minutes).
Are LEDs 1 and 2 on the
outdoor unit PCB OFF?
Refer to “Table of
Self-Diagnostic Functions and
Description of Alarm Displays.”
YES
NO
Turn OFF the indoor and
outdoor unit power.
Make necessary corrections.
Check the alarm contents.
*2 A minimum of 5 hours must have passed
after the power was turned ON to the
outdoor unit.
*3 All indoor units operate in all refrigerant
systems where the power is ON.
Make necessary
corrections
Turn OFF the indoor
and outdoor unit
Check the alarm
contents.
Is it OK to start the
compressors?
Turn ON the indoor and
outdoor unit power.
Short-circuit the mode change pin
(CN101) on the outdoor main unit
PCB. At the same time, short-circuit
the automatic address pin (CN100) for
1 second or longer, then release it.
Start indoor and outdoor unit
cooling operation.
LED 1 and 2 blink alternately.
Start indoor and outdoor unit
heating operation.
LED 1 and 2 blink alternately.
Short-circuit the automatic
address pin (CN100) on the
outdoor main unit PCB for
1 second or longer, then
release it.
Turn ON the indoor and
outdoor unit power.
Is it OK to start the
compressors?
*2
*2
*3
*3
Are LEDs 1 and 2 on the
outdoor unit PCB OFF?
YES
NO
Check that test run preparation is OK.
(Do not allow the short-circuited pins to remain short-circuited.)
NO
YES
Set the wired remote controller for test run.
Refer to the
remote controller
test-run settings.
Return remote control to normal mode
Check and make corrections according to
“Table of Self-Diagnostic Functions.”
Does system operate?
End test run.
*1
Note:
It is not necessary to remove
the socket that is used to
short-circuit the terminal plugs
from the outdoor sub unit PCBs.
<Outdoor unit control PCB>
Unit No. setting switch
(S006)
<Outdoor unit control PCB>
Unit No. setting switch
(S007)
YES
NO
Is the solenoid valve kit in
the indoor unit shared?
Was the setting change for the
shared solenoid valve kit performed?
Make a setting change.
*4 Refer to page 2-8
“Common solenoid
valve kit”.
*4
YES
NO
YES
2. Test Run Procedure
TD831143-00̲W-3WAY.indb 3
TD831143-00̲W-3WAY.indb 3
2008/12/01 16:22:34
2008/12/01 16:22:34
Summary of Contents for SPW-C0705DZH8
Page 2: ...i ...
Page 3: ...ii ...
Page 52: ...2 42 MEMO ...
Page 158: ...3 106 MEMO ...
Page 528: ...4 370 MEMO ...
Page 562: ...6 18 Electrical Data 1 2 3 4 5 6 7 8 2 Indoor Unit Schematic Diagram SPW KR254GXH56 A B ...
Page 575: ...6 31 Electrical Data 1 2 3 4 5 6 7 8 2 Indoor Unit Schematic Diagram SPW DR254GXH56 A B ...
Page 577: ...6 33 Electrical Data 1 2 3 4 5 6 7 8 2 Indoor Unit Schematic Diagram SPW DR364GXH56 A B ...
Page 579: ...6 35 Electrical Data 1 2 3 4 5 6 7 8 2 Indoor Unit Schematic Diagram SPW DR484GXH56 A B ...
Page 581: ...6 37 Electrical Data 1 2 3 4 5 6 7 8 2 Indoor Unit Schematic Diagram SPW DR764GXH56 A B ...
Page 583: ...6 39 Electrical Data 1 2 3 4 5 6 7 8 2 Indoor Unit Schematic Diagram SPW DR964GXH56 A B ...
Page 589: ...6 45 Electrical Data 1 2 3 4 5 6 7 8 2 Indoor Unit Schematic Diagram SPW GU055 075 105XH ...
Page 590: ...6 46 MEMO ...
Page 702: ...8 96 MEMO ...
Page 703: ...SANYO Electric Co Ltd Printed in Japan 200812B DC ...