<Cooling capacity>
If the corrected outdoor unit cooling capacity is greater than or equal to the total corrected unit cooling capacity of
all indoor units in that system (Ruc 1), then:
<Heating capacity>
<Heating>
Outdoor unit corrected heating capacity (5) = Outdoor unit rated heating capacity × Correction coefficient for
model ((1) Page 2-13) × Correction coefficient for outdoor temper-
ature conditions ((2) Page 2-13) × Correction coefficient for tubing
length and elevation difference ((3) Page 2-14) × Correction coeffi-
cient for frosting/defrosting ((4) Page 2-13)
However, if the outdoor unit corrected heating capacity [5] is greater than 100%, then the outdoor unit corrected heating
capacity is considered to be 100%.
Corrected heating capacity of each indoor unit (5) = Rated heating capacity for that indoor unit × Correction coef-
ficient for indoor temperature conditions at that indoor unit ((2) Page 2-14) × Distribution ratio based on tubing
length and elevation difference at that indoor unit.
However, the corrected heating capacity of each indoor unit is found as shown below.
If (2) < 100% and (2)
×
(3) > 100%: Corrected heating capacity for that indoor unit (5) = Rated heating capacity for that indoor unit
If (2) 100%: Corrected heating capacity for that indoor unit (5) = Rated heating capacity for that indoor unit
×
(2)
Characteristic graphs are shown on the pages listed above next to each correction item.
Find each correction coefficient from the appropriate conditions.
4. Calculating the actual indoor unit capacity based on the indoor/outdoor corrected capacity ratio
Calculate the actual capacity of each indoor unit from the values (found in (3)) for the corrected outdoor unit capac-
ity and the corrected capacity of each indoor unit.
Corrected indoor/outdoor capacity ratio during cooling (Ruc) = Total corrected cooling capacity of all indoor units in
that system / Corrected outdoor unit cooling capacity
Actual cooling capacity of each indoor unit (7) = Corrected cooling capacity of each indoor unit (5)
(In other words, the correction coefficient (6), based on the corrected indoor/outdoor capacity ratios for each
indoor unit, is 1.)
If the corrected outdoor unit cooling capacity is less than the total corrected unit cooling capacity of all indoor units
in that system (Ruc > 1), then:
(Actual cooling capacity of each indoor unit (7)) = (Corrected cooling capacity of each indoor unit (5)) × (0.25 ×
Ruc + 0.75) / Ruc
(In other words, the correction coefficient (6), based on the corrected indoor/outdoor capacity ratios for each
indoor unit, is the underlined part in the formula above.)
Corrected indoor/outdoor capacity ratio during heating (Ruh) = Total corrected heating capacity of all indoor units in
that system / Corrected outdoor unit heating capacity
If the corrected outdoor unit heating capacity is greater than or equal to the total corrected unit heating capacity of
all indoor units in that system (Ruh 1), then:
Actual heating capacity of each indoor unit (7) = Corrected heating capacity of each indoor unit (5)
(In other words, the correction coefficient (6), based on the corrected indoor/outdoor capacity ratios for each
indoor unit, is 1.)
If the corrected outdoor unit heating capacity is less than the total corrected unit heating capacity of all indoor units
in that system (Ruh > 1), then:
(Actual heating capacity of each indoor unit (7)) = (Corrected heating capacity of each indoor unit (5)) × (0.1 ×
Ruh + 0.9) / Ruh
(In other words, the correction coefficient (6), based on the corrected indoor/outdoor capacity ratios for each
indoor unit, is the underlined part in the formula above.)
2-12
Design of 3-WAY ECO-i SYSTEM
1
2
3
4
5
6
7
8
1. Model Selecting and Capacity Calculator
TD831143-00̲W-3WAY.indb 12
TD831143-00̲W-3WAY.indb 12
2008/12/01 16:15:42
2008/12/01 16:15:42
Summary of Contents for SPW-C0705DZH8
Page 2: ...i ...
Page 3: ...ii ...
Page 52: ...2 42 MEMO ...
Page 158: ...3 106 MEMO ...
Page 528: ...4 370 MEMO ...
Page 562: ...6 18 Electrical Data 1 2 3 4 5 6 7 8 2 Indoor Unit Schematic Diagram SPW KR254GXH56 A B ...
Page 575: ...6 31 Electrical Data 1 2 3 4 5 6 7 8 2 Indoor Unit Schematic Diagram SPW DR254GXH56 A B ...
Page 577: ...6 33 Electrical Data 1 2 3 4 5 6 7 8 2 Indoor Unit Schematic Diagram SPW DR364GXH56 A B ...
Page 579: ...6 35 Electrical Data 1 2 3 4 5 6 7 8 2 Indoor Unit Schematic Diagram SPW DR484GXH56 A B ...
Page 581: ...6 37 Electrical Data 1 2 3 4 5 6 7 8 2 Indoor Unit Schematic Diagram SPW DR764GXH56 A B ...
Page 583: ...6 39 Electrical Data 1 2 3 4 5 6 7 8 2 Indoor Unit Schematic Diagram SPW DR964GXH56 A B ...
Page 589: ...6 45 Electrical Data 1 2 3 4 5 6 7 8 2 Indoor Unit Schematic Diagram SPW GU055 075 105XH ...
Page 590: ...6 46 MEMO ...
Page 702: ...8 96 MEMO ...
Page 703: ...SANYO Electric Co Ltd Printed in Japan 200812B DC ...