4-362
1
2
3
4
5
6
7
8
3-WAY ECO-i SYSTEM Unit Specifi cations
12. Total Heat Exchanger with DX coil (GU Type)
12-2. Control Specifi cations
Unit specifi cations
MICROCOMPUTER CONTROL
Thermal modulation
Preset temperature range
Cooling
18 °C – 30 °C
Heating
16 °C – 30 °C
Auto
17 °C – 30 °C
Transpiration temperature control
preset value
Cooling
12 °C
Heating
40 °C
Setting
Mode change
Auto (*1), Heating, Cooling
Fan speed
Constant
Timer
OFF, ON, OFF Repeat
Alarm display (*2)
Serial communication errors or
setting errors
E**
Unregistered settings or setting
errors
L**
Safety device errors
P**
Thermistor trouble, etc.
F**
Compressor cover
H**
Heating Preparation
Indoor fan speed control
When the indoor heat exchanger
temperature is below 28 °C, below 25 °
C is rated wind velocity and below 1 °C
the wind stops. (Max. length of 6 min.)
Defrosting
Please refer to the service technical data of combined outdoor units.
Service functions
Temperature sensor indicator
function
All temperature sensors are call ready.
Service check (archival record)
indicator function
Records up to 4 service checks in the
order of the occurrence.
System Control
2 remote-controls
2 remote-controls connected (One as
a main remote-control, and one as
secondary remote-control.)
Group-control
Up to 8 units can be operated at once.
Other
Test run (Forced thermo ON)
Room temperature settings are
bypassed with forced operation.
Rated conditions
* 1. Only when all indoor units have an identical refrigerant system inside and the units are in the same group control system.
* 2. Please refer to the “Meaning of Alarm Messages” in section 5.
TD831143-00̲W-3WAY.indb 362
TD831143-00̲W-3WAY.indb 362
2008/12/01 17:25:20
2008/12/01 17:25:20
Summary of Contents for SPW-C0705DZH8
Page 2: ...i ...
Page 3: ...ii ...
Page 52: ...2 42 MEMO ...
Page 158: ...3 106 MEMO ...
Page 528: ...4 370 MEMO ...
Page 562: ...6 18 Electrical Data 1 2 3 4 5 6 7 8 2 Indoor Unit Schematic Diagram SPW KR254GXH56 A B ...
Page 575: ...6 31 Electrical Data 1 2 3 4 5 6 7 8 2 Indoor Unit Schematic Diagram SPW DR254GXH56 A B ...
Page 577: ...6 33 Electrical Data 1 2 3 4 5 6 7 8 2 Indoor Unit Schematic Diagram SPW DR364GXH56 A B ...
Page 579: ...6 35 Electrical Data 1 2 3 4 5 6 7 8 2 Indoor Unit Schematic Diagram SPW DR484GXH56 A B ...
Page 581: ...6 37 Electrical Data 1 2 3 4 5 6 7 8 2 Indoor Unit Schematic Diagram SPW DR764GXH56 A B ...
Page 583: ...6 39 Electrical Data 1 2 3 4 5 6 7 8 2 Indoor Unit Schematic Diagram SPW DR964GXH56 A B ...
Page 589: ...6 45 Electrical Data 1 2 3 4 5 6 7 8 2 Indoor Unit Schematic Diagram SPW GU055 075 105XH ...
Page 590: ...6 46 MEMO ...
Page 702: ...8 96 MEMO ...
Page 703: ...SANYO Electric Co Ltd Printed in Japan 200812B DC ...