3-4
Control of 3-WAY ECO-i SYSTEM
1
2
3
4
5
6
7
8
1. Main Operating Functions
1-2. Automatic Control for Heating and Cooling
Automatic Heating/Cooling Control
(1) When operation starts, heating or cooling is selected according to the set temperature and the room temperature.
Room temperature Set tempe 1
Cooling
Set temperature – 1 < Room temperature Set tempe 1
Monitoring mode (*1)
Room temperature < Set temperature – 1
Heating
*1: If the difference between the room temperature and set temperature is small when operation starts, the cooling
thermostat remains in standby status (OFF) until the temperature difference increases. When the temperature differ-
ence increases, either cooling operation or heating operation is selected. This standby status is known as “monitoring
mode.”
(2) After operation starts in the selected operating mode, the set temperature is automatically shifted by +2°C (cooling opera-
tion) or –2°C (heating operation).
Example: Temperature set on the remote controller is 20°C.
Selected operating mode
Shifted set temp.
Remote controller display
1
Cooling
22°C
20°C
2
Heating
18°C
20°C
(3) Operating mode changes (heating
cooling, cooling
heating) which occur during operation as a result of temperature
changes are handled as shown below.
Heating
cooling: Room temperature
Shifted set temperature (set tempe 2°C) + 0.5°C
Cooling
heating: Room temperature
Shifted set temperature (set temperature – 2°C) – 1.0°C
Example: Temperature set on the remote controller is 20°C.
Operating mode change
Shifted set temp.
1
Heating
Cooling
20 + 2 + 0.5 = 22.5°C or higher (*2)
2
Cooling
Heating
20 – 2 – 1.0 = 17°C or lower
*2: During heating operation when the body sensor is used, a temperature shift is applied to the intake temperature
detected by the sensor, in consideration of the difference in temperature at the top and bottom of the room. (Refer
to the “Room Temperature Control” item.) If this intake shift temperature is 4°C, then the heating
cooling change
occurs when the temperature detected by the body sensor is 26.5°C or higher.
(4) Cooling (heating) operation does not change if the room temperature changes from area C
A (or A
C) within 10
minutes after the compressor turns OFF. (Monitoring mode is excepted.)
(5) When the heating/cooling change occurs, the 4-way valve switches approximately 30 to 50 seconds after the compressor
turns ON.
Shifted set temp
Shifted set temp
Selected operating mode
Selected operating mode
Remote controller display
–2 deg
–1 deg
+1 deg
+3 deg
+2 deg
+2.5 deg
–3 deg
Thermostat
ON
ON
OFF
ON
OFF
ON
OFF
ON
ON OFF
OFF
A
B
C
Heating
Heating
Cooling
TD831143-00̲W-3WAY.indb 4
TD831143-00̲W-3WAY.indb 4
2008/12/01 10:26:20
2008/12/01 10:26:20
Summary of Contents for SPW-C0705DZH8
Page 2: ...i ...
Page 3: ...ii ...
Page 52: ...2 42 MEMO ...
Page 158: ...3 106 MEMO ...
Page 528: ...4 370 MEMO ...
Page 562: ...6 18 Electrical Data 1 2 3 4 5 6 7 8 2 Indoor Unit Schematic Diagram SPW KR254GXH56 A B ...
Page 575: ...6 31 Electrical Data 1 2 3 4 5 6 7 8 2 Indoor Unit Schematic Diagram SPW DR254GXH56 A B ...
Page 577: ...6 33 Electrical Data 1 2 3 4 5 6 7 8 2 Indoor Unit Schematic Diagram SPW DR364GXH56 A B ...
Page 579: ...6 35 Electrical Data 1 2 3 4 5 6 7 8 2 Indoor Unit Schematic Diagram SPW DR484GXH56 A B ...
Page 581: ...6 37 Electrical Data 1 2 3 4 5 6 7 8 2 Indoor Unit Schematic Diagram SPW DR764GXH56 A B ...
Page 583: ...6 39 Electrical Data 1 2 3 4 5 6 7 8 2 Indoor Unit Schematic Diagram SPW DR964GXH56 A B ...
Page 589: ...6 45 Electrical Data 1 2 3 4 5 6 7 8 2 Indoor Unit Schematic Diagram SPW GU055 075 105XH ...
Page 590: ...6 46 MEMO ...
Page 702: ...8 96 MEMO ...
Page 703: ...SANYO Electric Co Ltd Printed in Japan 200812B DC ...