44 - 104
Function Parameters
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
4
:
Clear UP/DOWN settings
. Press QUICK/JOG to clear
the set value of UP/DOWN.
5
:
Coast to stop
. Press QUICK/JOG to coast to stop.
6
:
Shift the running commands source
. Press
QUICK/JOG to shift the running commands source
(Keypad- Terminal- Communication)
7
:
Quick commission mode
(based on non-default
parameters)
Note
: Press QUICK/JOG to shift between forward rotation
and reverse rotation, the inverter does not record the state
after shifting during powering off. The inverter will run
according to parameter P00.13 during next powering on.
P07.03
QUICK/JOG
the shifting
sequence
selection of
running
command
When P07.02=6, set the shifting sequence of running
command channels.
0
: Keypad control
→
terminals control
→
communication
control
1
: Keypad control
←→
terminals control
2
: Keypad control
←→
communication control
3
: Terminals control
←→
communication control
0
○
P07.04
STOP/RST
stop function
Select the stop function by STOP/RST. STOP/RST is
effective in any state for the keypad reset.
0
: Only valid for the panel control
1
: Both valid for panel and terminals control
2
: Both valid for panel and communication control
3
: Valid for all control modes
0
○
P07.05
Displayed
parameters 1
of running state
0x0000~0xFFFF
BIT0
: running frequency (Hz on)
BIT1
: set frequency(Hz flickering)
BIT2
: bus voltage (Hz on)
BIT3
: output voltage(V on)
BIT4
: output current(A on)
BIT5
: running rotation speed (rpm on)
BIT6
: output power(% on)
BIT7
: output torque(% on)
BIT8
: PID reference(% flickering)
BIT9
: PID feedback value(% on)
0x03FF
○