Function Parameters
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
P08.33
FDT retention
detection value
“frequency level detect FDT”. Until the output frequency
decreases to a value lower than the corresponding
frequency (
FDT retention detection value
), the signal is
valid. Below is a diagram:
Setting range of P08.32: 0.00Hz~P00.03 (Max. frequency)
Setting range of P08.33: 0.0~100.0% (FDT electrical level)
5.0%
○
P08.36
Frequency
arrival
detection value
When the output frequency is among the below or above
range of the set frequency, the multi-function digital output
terminal will output the signal of “frequency arrival”, see the
diagram below for detailed information:
The setting range: 0.00Hz~P00.03 (the Max. frequency)
0.00Hz
○
P08.37
Energy Braking
enable
This parameter is used to control the internal braking unit.
0
: Disabled
1
: Enabled
Note
: Only applied to internal braking unit.
0
○
P08.38
Energy Braking
threshold
voltage
This parameter sets the DC bus voltage above which the internal braking
unit starts to work. Adjust the voltage appropriately to brake the load.
The setting range: 200.0~2000.0V
The recommended setting range: 375~400V
380.0V
○