58 - 104
Function Parameters
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
P10 Group Multi-step speed control
P10.02
Multi-step
speed 0
100.0% of the frequency setting corresponds to the Max.
Frequency P00.03.
When selecting multi-step running, set P10.02~P10.33 to
define the running frequency and direction of all stages.
Note: The symbol of multi-step determines the running
direction. The negative value means reverse rotation.
Multi-step speeds are in the range of -f
max
~f
max
and they can
be adjusted continuously.
CV10 inverters can set 16 stages speed, selected by the
combination of multi-step terminals 1~4, corresponding to
the speed 0 to speed 15.
When S1=S2=S3=S4=OFF, the frequency input manner is selected
via code P00.06 or P00.07. When all S1=S2=S3=S4 terminals
aren’t off, it runs at multi-step which takes precedence of keypad,
0.0%
○
P10.04
Multi-step
speed 1
0.0%
○
P10.06
Multi-step
speed 2
0.0%
○
P10.08
Multi-step
speed 3
0.0%
○
P10.10
Multi-step
speed 4
0.0%
○
P10.12
Multi-step
speed 5
0.0%
○
P10.14
Multi-step
speed 6
0.0%
○
P10.16
Multi-step
speed 7
0.0%
○
P10.18
Multi-step
speed 8
0.0%
○
P10.20
Multi-step
speed 9
0.0%
○
P10.22
Multi-step
speed 10
0.0%
○
P10.24
Multi-step
speed 11
0.0%
○