54 - 104
Function Parameters
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
P08.44
UP/DOWN
terminals
control setting
0x00~0x221
LED ones
: frequency enabling selection
0
: UP/DOWN terminals setting valid
1
: UP/DOWN terminals setting invalid
LED tens
: frequency control selection
0
: Only valid when P00.06=0 or P00.07=0
1
: All frequency means are valid
2
: When the multi-step are priority, it is invalid to the
multi-step
LED hundreds
: action selection when stop
0
: Setting valid
1
: Valid in the running, clear after stop
2
: Valid in the running, clear after receiving the stop
commands
0x000
○
P08.45
UP terminal
frequency
changing ratio
0.01~50.00 Hz/s
0.50 Hz/s
○
P08.46
DOWN terminal
frequency
changing ratio
0.01~50.00 Hz/s
0.50 Hz/s
○
P08.47
Action
selection for
frequency
settings on
power off
0x000~0x111
LED ones
: Action for digital adjustable frequency on power off
0
: Save on power off
1
: Clear on power off
LED tens
: Action for MODBUS frequency setting on power off
0
: Save on power off
1
: Clear on power off
LED hundreds
: Action for other-mode frequency setting on
power off
0
: Save on power off
1
: Clear on power off
0x000
○
P08.50
Magnetic flux
braking
This function code is used to enable magnetic flux.
0
: Invalid.
100~150
: the bigger the coefficient, the bigger the braking
strength.
This inverter can slow down the motor by increasing the magnetic
flux. The energy generated by the motor during braking can be
transformed into heat energy by increasing the magnetic flux.
The inverter monitors the state of the motor continuously
even during the magnetic flux period. So the magnetic flux
0
●