Function Parameters
37 - 104
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
P05.11
Switch filter
time
Set the sample filter time of S1~S5 terminals. If the interference is
strong, increase the parameter to avoid the wrong operation.
0.000~1.000s
0.010s
○
P05.12
Virtual
terminals
setting
Enable the input function of virtual terminals at the
communication mode.
0: Virtual terminals is invalid
1: MODBUS communication virtual terminals are valid
0
◎
P05.13
Terminals
control running
mode
Set the operation mode of the terminals control
0: 2-wire control 1
, comply the enable with the direction. This
mode is widely used. It determines the rotation direction by the
defined FWD and REV terminals command.
FWD
REV
COM
K1
K2
Running
command
FWD
REV
OFF
OFF
OFF
OFF
ON
ON
ON
ON
Stopping
Hold on
Forward
running
Reverse
running
1: 2-wire control 2
;
Separate the enable from the direction. FWD
defined by this mode is the enabling one. The direction depends
on the state of the defined REV.
2: 3-wire control 1
; SIn is the enabling terminal in this mode, and
the running command is caused by FWD and the direction is
controlled by REV. SIn is normal closed.
0
◎