Function Parameters
47 - 104
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
P07.27
Current fault
type
0
: No fault
4
: OC1 (Over-current when acceleration)
5
: OC2 (Over-current when deceleration)
6
: OC3 (Over-current when constant speed running)
7
: OV1 (Over-voltage when acceleration)
8
: OV2 (Over-voltage when deceleration)
9
: OV3 (Over-voltage when constant speed running)
10
: UV (DC bus Under-voltage)
11
: OL1 (Motor overload)
12
: OL2 (Inverter overload)
15
: OH1 (Overheat of the rectifier module)
16
: OH2 (Overheat fault of the inverter module)
17
: EF (External fault)
18
: CE (RS485 communication error)
21
: EEP (EEPROM operation fault)
22
: PIDE (PID feedback fault)
24
: END (Running time arrival)
25
: OL3 (Electrical overload)
36
: LL (Underload fault)
●
P07.28
Previous fault
type
●
P07.29
Previous 2 fault
type
●
P07.30
Previous 3 fault
type
●
P07.31
Previous 4 fault
type
●
P07.32
Previous 5 fault
type
●
P07.33
Current fault
running frequency
0.00Hz
●
P07.34
Ramp reference
frequency at
current fault
0.00Hz
●
P07.35
Output voltage
at current fault
0V
●
P07.36
Output current
at current fault
0.0A
●
P07.37
Bus voltage at
current fault
0.0V
●
P07.38
Max. temperature
at current fault
0.0
●
Summary of Contents for CV10-002-S2
Page 1: ...USER MANUAL INVERTER CONTROLVIT CV10...
Page 2: ......
Page 67: ...Function Parameters 67 104 5 2 Diagram of quick start...
Page 100: ......
Page 101: ......
Page 102: ......
Page 103: ......