28 - 104
Function Parameters
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
Setting range: 0.0~50.0s
P01.03
The braking
current before
starting
The inverter will carry out DC braking at the braking current
set before starting and it will speed up after the DC braking
time. If the DC braking time is set to 0, the DC braking is
invalid.
The stronger the braking current, the bigger the braking
power. The DC braking current before starting means the
percentage of the rated current of the inverter.
The setting range of P01.03: 0.0~100.0%
The setting range of P01.04: 0.0~50.0s
0.0%
◎
P01.04
The braking
time before
starting
0.00s
◎
P01.05
ACC/DEC
selection
0: Linear type
The changing mode of the frequency during start-up and
running.
The output frequency increases or decreases linearly.
0
◎
P01.08
Stop selection
0: Decelerate to stop
. After the stop command becomes
valid, the inverter decelerates to decrease the output
frequency during the set time. When the frequency
decreases to 0 Hz, the inverter stops.
1: Coast to stop
. After the stop command becomes valid,
the inverter ceases the output immediately. And the load
coasts to stop at the mechanical inertia.
0
○
P01.09
Starting
frequency of
DC braking
Starting frequency of DC braking
: start the DC braking
when running frequency reaches starting frequency
determined by P1.09.
Waiting time before DC braking
: Inverters block the output
before starting the DC braking. After this waiting time, the
DC braking will be started so as to prevent over-current fault
0.00Hz
○
P01.10
Waiting time
0.00s
○