Function Parameters
23 - 104
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
P00 Group Basic function group
P00.00
Speed control
mode
2: SVPWM control
(Suitable for Asynchronous Motor)
Suitable in cases where it does not need high control
accuracy, such as the load of fan and pump. One inverter
can drive multiple motors.
2
◎
P00.01
Run command
channel
Select the run command channel of the inverter.
The control command of the inverter includes: start, stop,
forward, reverse, jogging and fault reset.
0: Keypad running command channel
(“LOCAL/REMOT”
light off)
Carry out the command control by RUN, STOP/RST on the
keypad.
Set the multi-function key QUICK/JOG to FWD/REV shifting
function (P07.02=3) to change the running direction; press
RUN
and
STOP/RST
simultaneously in running state to
make the inverter coast to stop.
1:Terminal running command channel
(“LOCAL/REMOT”
flickering)
Carry out the running command control by the forward
rotation, reverse rotation and forward jogging and reverse
jogging of the multi-function terminals
2: Communication running command channel
(“LOCAL/REMOT” on)
;
The running command is controlled by the upper monitor via
communication
0
○
P00.03
Max. output
frequency
This parameter is used to set the maximum output frequency
of the inverter. Users need to pay attention to this parameter
because it is the foundation of the frequency setting and the
speed of acceleration and deceleration.
Setting range: P00.04~400.00Hz
50.00Hz
◎
P00.04
Upper limit of
the running
frequency
The upper limit of the running frequency is the upper limit of
the output frequency of the inverter which is lower than or
equal to the maximum frequency.
Setting range:P00.05~P00.03 (Max. output frequency)
50.00Hz
◎