Reference Manual
00809-0100-4663, Rev BA
January 2010
Rosemount 8732
A-4
F
OUNDATION
™
FIELDBUS
SPECIFICATIONS
Schedule Entries
Seven (7)
Links
Twenty (20)
Virtual Communications Relationships (VCRs)
One (1) predefined (F6, F7) Nineteen (19) configurable (see Table 1)
Table A-1. Block Information
Reverse Flow
Detects and reports reverse flow
Software Lockout
A write-lock switch and software lockout are provided in the resource function
block.
Turn-on Time
5 minutes to rated accuracy from power up; 10 seconds from power
interruption.
Start-up Time
50 ms from zero flow.
Low Flow Cutoff
Adjustable between 0.01 and 38.37 ft/s (0.003 and 11.7 m/s). Below selected
value, output is driven to the zero flow rate signal level.
Overrange Capability
Signal output will remain linear until 110% of upper range value or 44 ft/s (13
m/s). The signal output will remain constant above these values. Out of range
message displayed on local display and field communicator.
Damping
Adjustable between 0 and 256 seconds.
Sensor Compensation
Rosemount sensors are flow-calibrated and assigned a calibration factor at
the factory. The calibration factor is entered into the transmitter, enabling
interchangeability of sensors without calculations or a compromise in
standard accuracy.
Block
Execution Time (Milliseconds)
Resource (RB)
—
Transducer (TB)
—
Analog Input (AI)
10
Proportional/Integral/
Derivative (PID)
10
Integrator (INT)
10
Arithmetic (AR)
10
Summary of Contents for 8732 Series
Page 2: ......
Page 4: ......
Page 10: ...Reference Manual 00809 0100 4663 Rev BA January 2010 Rosemount 8732 TOC 6 ...
Page 26: ...Reference Manual 00809 0100 4663 Rev BA January 2010 Rosemount 8732 2 14 ...
Page 38: ...Reference Manual 00809 0100 4663 Rev BA January 2010 Rosemount 8732 3 12 ...
Page 92: ...Reference Manual 00809 0100 4663 Rev BA January 2010 Rosemount 8732 A 8 ...
Page 186: ...Reference Manual 00809 0100 4663 Rev BA January 2010 Rosemount 8732 H 8 ...
Page 189: ......