Reference Manual
00809-0100-4663, Rev BA
January 2010
Rosemount 8732
4-12
ADVANCED
CONFIGURATION
In addition to the basic configuration options and the diagnostic information
and controls, the 8732 has many advanced functions that can also be
configured as required by the application.
DETAILED SETUP
The detailed setup function provides access to other parameters within the
transmitter that can be configured such as coil drive frequency, output
parameters, local display configuration, and other general information about
the device.
Additional Parameters
The additional parameters menu provides a means to configure optional
parameters within the 8732E transmitter.
Coil Drive Frequency
Coil drive frequency allows pulse-rate selection of the sensor coils.
5 Hz
The standard coil drive frequency is 5 Hz, which is sufficient for nearly all
applications.
37 Hz
If the process fluid causes a noisy or unstable output, increase the coil drive
frequency to 37 Hz. If the 37 Hz mode is selected, perform the auto zero
function.
Density Value
The density value is used to convert from a volumetric flow rate to a mass flow
rate using the following equation:
Q
m
= Q
v
Where:
Q
m
is the mass flow rate
Q
v
is the volumetric flow rate, and
is the fluid density
NOTE
A density value is required to configure the flow units for mass flow rate
measurement.
Sensor Range: EU at 100%
This parameter is the maximum value that the PV Range value can be set to.
This is the upper measuring limit of the transmitter and sensor.
Sensor Range: EU at 0%
This parameter is the minimum value that the PV Range value can be set to.
This is the lower measuring limit of the transmitter and sensor.
375
Transducer Block
375
Transducer Block, Detailed
Setup
375 Transducer Block, Detailed Setup, Additional Params
375 Transducer Block, Detailed Setup, Additional Params
375 Transducer Block, Detailed Setup, Additional Params
375 Transducer Block, Detailed Setup, Additional Params
Summary of Contents for 8732 Series
Page 2: ......
Page 4: ......
Page 10: ...Reference Manual 00809 0100 4663 Rev BA January 2010 Rosemount 8732 TOC 6 ...
Page 26: ...Reference Manual 00809 0100 4663 Rev BA January 2010 Rosemount 8732 2 14 ...
Page 38: ...Reference Manual 00809 0100 4663 Rev BA January 2010 Rosemount 8732 3 12 ...
Page 92: ...Reference Manual 00809 0100 4663 Rev BA January 2010 Rosemount 8732 A 8 ...
Page 186: ...Reference Manual 00809 0100 4663 Rev BA January 2010 Rosemount 8732 H 8 ...
Page 189: ......