4-7
Level Controller Configuration
Set Mode Shed Options
(Failure Condition)
See page 3-9 for details about Mode Shed.
Shed Action
Shed Action selects whether the controller remains at its present value
(hold output) or goes to the shed output value if the Level Controller
determines that the level measurement has failed.
Factory Default:
Go to shed output
Valid Options:
Hold output, go to shed output
.
Shed Output
This selection sets the control output value during a mode shed action.
If the Level Controller determines that the level measurement is bad,
AND
the Mode Shed Action is set to “go to shed output,” the Level
Controller will then automatically set the control output to this value.
This value is entered as a percentage of controller output. For example,
a mode shed output value of 25% corresponds to 8 mA.
(25%
3
(20 – 4 mA) + 4 mA = 8 mA)
Factory Default:
0%
Valid Range:
–2.5 to 112.5% (3.6 to 22 mA)
Shed Return
This selection determines whether the controller returns from the mode
shed routine if the failed level measurement condition ends.
Factory Default:
Return
Valid Options:
Return, no return
Set Manual Output
Manual Rate Limit
Output rate limits define the maximum rate of change of the control
output when the controller is in manual mode. Setting this variable to
0.0 disables manual output rate limits.
Factory Default:
0.0 (No rate limit)
Valid Range:
> 0.0% per second
Manual Output
Setting manual output is a two step process. First, set the target mode
to manual (MAN). Second, set the manual output value.
When in manual output mode, the operator enters a value as a
percentage of controller output. For example, a manual output
value of 25% corresponds to 8 mA.
(25%
3
(20 – 4 mA) + 4 mA = 8 mA)
Valid Range:
–0.625 to 105% (3.9 to 20.8 mA)
HART Comm.
6, 2, 3, 3
HART Comm.
6, 2, 3, 4
HART Comm.
6, 2, 3, 5
HART Comm.
6, 2, 5, 2
HART Comm
4
Summary of Contents for 3095
Page 2: ......
Page 4: ......
Page 8: ...viii ...
Page 10: ...Rosemount Model 3095 Multivariable Level Controller 1 2 ...
Page 42: ...Rosemount Model 3095 Multivariable Level Controller 3 10 ...
Page 74: ...Rosemount Model 3095 Multivariable Level Controller 5 18 ...
Page 98: ...Rosemount Model 3095 Multivariable Level Controller B 4 ...
Page 101: ...C 3 Approval Drawings FIGURE 3 1 continued 3095 1025A02A ...
Page 102: ...Rosemount Model 3095 Multivariable Level Controller C 4 FIGURE 3 1 continued 3095 1025A03A ...
Page 103: ...C 5 Approval Drawings FIGURE 3 2 Index of I S F M for 3095 3095 1020A01A ...
Page 104: ...Rosemount Model 3095 Multivariable Level Controller C 6 FIGURE 3 2 continued 3095 1020A02A ...
Page 105: ...C 7 Approval Drawings FIGURE 3 2 continued 3095 1020A03A ...
Page 106: ...Rosemount Model 3095 Multivariable Level Controller C 8 FIGURE 3 2 continued 3095 1020A04A ...
Page 107: ...C 9 Approval Drawings FIGURE 3 2 continued 3095 1020A05A ...
Page 108: ...Rosemount Model 3095 Multivariable Level Controller C 10 FIGURE 3 2 continued 3095 1020A06A ...
Page 110: ...Rosemount Model 3095 Multivariable Level Controller C 12 FIGURE 3 3 continued 3095 1024A02A ...
Page 111: ...C 13 Approval Drawings FIGURE 3 3 continued 3095 1024A03A ...
Page 113: ...C 15 Approval Drawings FIGURE 3 4 continued 3095 1021A02A ...
Page 114: ...Rosemount Model 3095 Multivariable Level Controller C 16 FIGURE 3 4 continued 3095 1021A03A ...