Rosemount Model 3095 Multivariable
™
Level Controller
5-4
Overrange Conditions
Overrange conditions are typically caused by an error in which the
sensor or level measurements have reached an overrange condition
where substitute values are being used.
TABLE 5-3. Corrective Action:
Overrange Conditions.
Sensor Limits and Alarm
Abbreviation
Table 5-4 identifies sensor limits. Standard alarm abbreviations used
in alarm Tables 5-3 and 5-4 are:
LRL
Lower Range Limits
URL
Upper Range Limits
LRV
Lower Range Value
URV
Upper Range Value
URL+
URL + (10%URL)
(For example, URL+ = 250 + (0.10
3
250) = 275
LRL–
LRL – (10%LRL)
(For example, LRL– = –250 –[0.10
3
(250)] = –275
TABLE 5-4. Level Controller
Sensor Limits.
(1) LRL– is equal to LRV and lower sensor trim limits.
(2) URL+ is equal to URV and upper sensor trim limits.
(3) In the fixed temperature mode, PT range is –459 to 3500 °F (–273 to 1927 °C).
(4) For Alpha Two field trial units, PT URL is 800 °F (427 °C).
Alarm text as displayed in
Diagnostics, Error Info
Corrective Action
DP above URL+
These displays indicate that the device differential pressure reading exceeds its sensor limits by more than 10%.
There are two possible causes; either the device is overpressured (underpressured), or it has a sensor
malfunction. Check the pressure input to the device. If an overpressure (underpressure) condition exists, correct it.
If not, replace the sensor module as described on page 5-11.
DP below LRL–
Working Pressure above URL+
These displays indicate that the device absolute pressure reading exceeds its sensor limits by more than 10%.
There are two possible causes; either the device is overpressured (underpressured), or it has a sensor
malfunction. Check the pressure input to the device. If an overpressure (underpressure) condition exists, correct it.
If not, replace the sensor module as described on page 5-11.
Working Pressure below LRL–
PT above URL+
Check the device RTD connector and RTD screw terminals to ensure that the RTD cable is properly connected.
Verify that the process temperature is between –40 °F and 1200 °F.
PT below LRL–
ST above URL+
These displays indicate that the ambient temperature limit of the device is being exceeded. Verify that the device
ambient temperature is between –40 °F and 185 °F. If device temperature exceeds these limits, correct the
temperature. If device temperature is within these limits, replace the sensor module as described on page 5-11.
ST below LRL–
Sensor
LRL–
(1)
LRL
URL
URL+
(2)
DP Range 2
–275 inH
2
0 at 68 °F
–250 inH
2
0 at 68 °F
250 inH
2
0 at 68 °F
275 inH
2
0 at 68 °F
DP Range 3
–913 inH
2
0 at 68 °F
–830 inH
2
0 at 68 °F
830 inH
2
0 at 68 °F
913 inH
2
0 at 68 °F
PT
(3)
–44 °F (–42 °C)
–40 °F (–40 °C)
1200 °F (649 °C)
(4)
1220 °F (660 °C)
Sensor Temperature
–44 °C
–40 °C
85 °C
93.5 °C
Summary of Contents for 3095
Page 2: ......
Page 4: ......
Page 8: ...viii ...
Page 10: ...Rosemount Model 3095 Multivariable Level Controller 1 2 ...
Page 42: ...Rosemount Model 3095 Multivariable Level Controller 3 10 ...
Page 74: ...Rosemount Model 3095 Multivariable Level Controller 5 18 ...
Page 98: ...Rosemount Model 3095 Multivariable Level Controller B 4 ...
Page 101: ...C 3 Approval Drawings FIGURE 3 1 continued 3095 1025A02A ...
Page 102: ...Rosemount Model 3095 Multivariable Level Controller C 4 FIGURE 3 1 continued 3095 1025A03A ...
Page 103: ...C 5 Approval Drawings FIGURE 3 2 Index of I S F M for 3095 3095 1020A01A ...
Page 104: ...Rosemount Model 3095 Multivariable Level Controller C 6 FIGURE 3 2 continued 3095 1020A02A ...
Page 105: ...C 7 Approval Drawings FIGURE 3 2 continued 3095 1020A03A ...
Page 106: ...Rosemount Model 3095 Multivariable Level Controller C 8 FIGURE 3 2 continued 3095 1020A04A ...
Page 107: ...C 9 Approval Drawings FIGURE 3 2 continued 3095 1020A05A ...
Page 108: ...Rosemount Model 3095 Multivariable Level Controller C 10 FIGURE 3 2 continued 3095 1020A06A ...
Page 110: ...Rosemount Model 3095 Multivariable Level Controller C 12 FIGURE 3 3 continued 3095 1024A02A ...
Page 111: ...C 13 Approval Drawings FIGURE 3 3 continued 3095 1024A03A ...
Page 113: ...C 15 Approval Drawings FIGURE 3 4 continued 3095 1021A02A ...
Page 114: ...Rosemount Model 3095 Multivariable Level Controller C 16 FIGURE 3 4 continued 3095 1021A03A ...