Troubleshooting and Maintenance
Unexpected Process Variable
(PV) Readings
Use a Model 275 HART Communicator to display the current process
variables. Before connecting a HART-based communicator in an
explosive atmosphere, make sure the instruments in the loop are
installed in accordance with intrinsically safe or non-incendive field
wiring practices.
The following performance limitations may inhibit efficient or safe
operation. Critical applications should have appropriate diagnostic and
backup systems in place.
Pressure devices contain an internal fill fluid. It is used to transmit the
process pressure through the isolating diaphragms to the pressure
sensing element. In rare cases, oil loss paths in oil-filled pressure
devices can be created. Possible causes include:
• Physical damage to the isolator diaphragms.
• Process fluid freezing.
• Isolator corrosion due to an incompatible process fluid.
A device with oil fill fluid loss may continue to perform normally for a
period of time. Sustained oil loss will eventually cause one or more of
the operating parameters to exceed published specifications while a
small drift in operating point output continues. Symptoms of advanced
oil loss and other unrelated problems include:
• Sustained drift rate in true zero and span or operating point
output or both.
• Sluggish response to increasing or decreasing pressure or both.
• Limited output rate or very nonlinear output or both.
• Change in output process noise.
• Noticeable drift in operating point output.
• Abrupt increase in drift rate of true zero or span or both.
• Unstable output.
• Output saturated high or low.
Summary of Contents for 3095
Page 2: ......
Page 4: ......
Page 8: ...viii ...
Page 10: ...Rosemount Model 3095 Multivariable Level Controller 1 2 ...
Page 42: ...Rosemount Model 3095 Multivariable Level Controller 3 10 ...
Page 74: ...Rosemount Model 3095 Multivariable Level Controller 5 18 ...
Page 98: ...Rosemount Model 3095 Multivariable Level Controller B 4 ...
Page 101: ...C 3 Approval Drawings FIGURE 3 1 continued 3095 1025A02A ...
Page 102: ...Rosemount Model 3095 Multivariable Level Controller C 4 FIGURE 3 1 continued 3095 1025A03A ...
Page 103: ...C 5 Approval Drawings FIGURE 3 2 Index of I S F M for 3095 3095 1020A01A ...
Page 104: ...Rosemount Model 3095 Multivariable Level Controller C 6 FIGURE 3 2 continued 3095 1020A02A ...
Page 105: ...C 7 Approval Drawings FIGURE 3 2 continued 3095 1020A03A ...
Page 106: ...Rosemount Model 3095 Multivariable Level Controller C 8 FIGURE 3 2 continued 3095 1020A04A ...
Page 107: ...C 9 Approval Drawings FIGURE 3 2 continued 3095 1020A05A ...
Page 108: ...Rosemount Model 3095 Multivariable Level Controller C 10 FIGURE 3 2 continued 3095 1020A06A ...
Page 110: ...Rosemount Model 3095 Multivariable Level Controller C 12 FIGURE 3 3 continued 3095 1024A02A ...
Page 111: ...C 13 Approval Drawings FIGURE 3 3 continued 3095 1024A03A ...
Page 113: ...C 15 Approval Drawings FIGURE 3 4 continued 3095 1021A02A ...
Page 114: ...Rosemount Model 3095 Multivariable Level Controller C 16 FIGURE 3 4 continued 3095 1021A03A ...