Rosemount Model 3095 Multivariable Level Controller
B-2
ACCESSORIES
Model 1199 Remote
Diaphragm Seals
The Level Controller can be supplied with Rosemount’s complete family
of Model 1199 Diaphragm Seals for capillary or direct mount to the
tank. Refer to the Model 1199 Filled Systems PDS, 00813-0100-4016,
for additional information.
Model 305 Integral Manifold
The Level Controller can be fully assembled to the Model 305 Integral
Manifold. The system is fully assembled, filled, calibrated, and
pressure tested by the factory. Refer to PDS 00813-0100-4733 for
additional information.
SST Mounting Brackets
Optional mounting brackets available with the Level Controller
facilitate mounting to panel, wall, or 2-inch pipe. The bracket option for
use with the Coplanar
™
flange is 316 SST with 316 SST bolts.
Transient Protection
Terminal Block
The transient protection terminal block option increases the Model
3095 Level Controller’s ability to withstand electrical transients
induced by lightning, welding, or heavy electrical equipment.
The Level Controller, with integral transient protection installed,
meets the standard performance specifications as outlined in this
product manual.
Transient protection terminal blocks can be ordered factory-installed,
or they can be ordered as a spare part to retrofit existing Model 3095
Level Controllers already in the field. The Rosemount spare part
number for the transient protection terminal block is 03095-0964-0002.
Installation Procedure
The transient protection terminal block is shipped installed when
ordered at the same time as the Level Controller. Use the following
procedure to install this terminal block when this option is ordered as a
spare part or retrofit.
1. Remove the cover above the side marked FIELD TERMINALS
on the Level Controller electronics housing. Do not remove the
instrument cover in explosive atmospheres when the circuit is
alive.
2. Loosen the two terminal block mounting screws and pull the
standard terminal block out.
3. If present, transfer the signal wires from the old terminal block to
the transient protection terminal block. Be sure that the + signal
wire is reconnected to the SIG + terminal, and the – signal wire is
reconnected to the SIG – terminal.
4. Install the terminal block by positioning the terminal block above
the post connector pins and pressing into place.
5. Use the captive mounting screws on the terminal block to secure
it to the electronics housing.
6. Ground the terminal block using one of the options described on
page 2-22.
7. Replace the Level Controller cover. Both transmitter covers must
be fully engaged to meet explosion-proof requirements.
8. (Optional) If desired, re-trim the Level Controller (see page 4-10).
NOTE
Installation of the Transient Protection Terminal Block does not
provide transient protection unless the Level Controller is properly
grounded. See page 2-22 for grounding information.
Summary of Contents for 3095
Page 2: ......
Page 4: ......
Page 8: ...viii ...
Page 10: ...Rosemount Model 3095 Multivariable Level Controller 1 2 ...
Page 42: ...Rosemount Model 3095 Multivariable Level Controller 3 10 ...
Page 74: ...Rosemount Model 3095 Multivariable Level Controller 5 18 ...
Page 98: ...Rosemount Model 3095 Multivariable Level Controller B 4 ...
Page 101: ...C 3 Approval Drawings FIGURE 3 1 continued 3095 1025A02A ...
Page 102: ...Rosemount Model 3095 Multivariable Level Controller C 4 FIGURE 3 1 continued 3095 1025A03A ...
Page 103: ...C 5 Approval Drawings FIGURE 3 2 Index of I S F M for 3095 3095 1020A01A ...
Page 104: ...Rosemount Model 3095 Multivariable Level Controller C 6 FIGURE 3 2 continued 3095 1020A02A ...
Page 105: ...C 7 Approval Drawings FIGURE 3 2 continued 3095 1020A03A ...
Page 106: ...Rosemount Model 3095 Multivariable Level Controller C 8 FIGURE 3 2 continued 3095 1020A04A ...
Page 107: ...C 9 Approval Drawings FIGURE 3 2 continued 3095 1020A05A ...
Page 108: ...Rosemount Model 3095 Multivariable Level Controller C 10 FIGURE 3 2 continued 3095 1020A06A ...
Page 110: ...Rosemount Model 3095 Multivariable Level Controller C 12 FIGURE 3 3 continued 3095 1024A02A ...
Page 111: ...C 13 Approval Drawings FIGURE 3 3 continued 3095 1024A03A ...
Page 113: ...C 15 Approval Drawings FIGURE 3 4 continued 3095 1021A02A ...
Page 114: ...Rosemount Model 3095 Multivariable Level Controller C 16 FIGURE 3 4 continued 3095 1021A03A ...