![Rosemount 3095 Product Manual Download Page 48](http://html.mh-extra.com/html/rosemount/3095/3095_product-manual_1487360048.webp)
Rosemount Model 3095 Multivariable
™
Level Controller
4-6
Adaptive Bias Control
(ABC) Settings
Adaptive Bias Control (ABC) provides a method to create a steady state
deadband for the level controller. Once the desired level is obtained, the
controller could repeatedly open and close the valve for very small
differences between the setpoint and the actual tank level. ABC allows
the controller to determine that the level is stable, and to not change the
valve position except when a larger difference occurs between the
setpoint and the actual tank level. This saves on unnecessary valve wear.
ABC is only available if the control mode is set to P or PD.
Bias is modified when ABC is enabled in Auto mode. See page 3-7 for
details about ABC.
Adaptive Bias Control
This selection enables or disables the ABC algorithm.
Factory Default:
Off
Valid Range:
On, Off
ABC Static Error
This selection sets the minimum amount that the level must differ from
the setpoint before the ABC algorithm changes the bias level.
This parameter is set in level units.
Factory Default:
1.0 inch
Valid Range:
0.0 to 20 in.
ABC Stability Threshold
The stability threshold is the user-defined limit on the rate of change
of level. When inside this limit, the algorithm considers the process
to be stable.
This parameter is set in level units per second.
Factory Default:
1.0 inch per second
Valid Range:
0 – 10 in./sec.
Set Power-Up Output
Power-Up Output
The user can set the control output value when the Level Controller
powers up or the Level Controller is reset.
This value is entered as a percentage of controller output. For example,
a power-up output value of 50% corresponds to 12 mA.
(50%
3
(20 – 4 mA) + 4 mA = 12 mA)
Factory Default:
0%
Valid Range:
–0.625 to 105% (3.9 to 20.8 mA)
(Saturation Low to Saturation High)
HART Comm.
6, 2, 1, 8
HART Comm.
6, 2, 1, 9
HART Comm.
6, 2, 1
HART Comm.
6, 2, 3, 6
Summary of Contents for 3095
Page 2: ......
Page 4: ......
Page 8: ...viii ...
Page 10: ...Rosemount Model 3095 Multivariable Level Controller 1 2 ...
Page 42: ...Rosemount Model 3095 Multivariable Level Controller 3 10 ...
Page 74: ...Rosemount Model 3095 Multivariable Level Controller 5 18 ...
Page 98: ...Rosemount Model 3095 Multivariable Level Controller B 4 ...
Page 101: ...C 3 Approval Drawings FIGURE 3 1 continued 3095 1025A02A ...
Page 102: ...Rosemount Model 3095 Multivariable Level Controller C 4 FIGURE 3 1 continued 3095 1025A03A ...
Page 103: ...C 5 Approval Drawings FIGURE 3 2 Index of I S F M for 3095 3095 1020A01A ...
Page 104: ...Rosemount Model 3095 Multivariable Level Controller C 6 FIGURE 3 2 continued 3095 1020A02A ...
Page 105: ...C 7 Approval Drawings FIGURE 3 2 continued 3095 1020A03A ...
Page 106: ...Rosemount Model 3095 Multivariable Level Controller C 8 FIGURE 3 2 continued 3095 1020A04A ...
Page 107: ...C 9 Approval Drawings FIGURE 3 2 continued 3095 1020A05A ...
Page 108: ...Rosemount Model 3095 Multivariable Level Controller C 10 FIGURE 3 2 continued 3095 1020A06A ...
Page 110: ...Rosemount Model 3095 Multivariable Level Controller C 12 FIGURE 3 3 continued 3095 1024A02A ...
Page 111: ...C 13 Approval Drawings FIGURE 3 3 continued 3095 1024A03A ...
Page 113: ...C 15 Approval Drawings FIGURE 3 4 continued 3095 1021A02A ...
Page 114: ...Rosemount Model 3095 Multivariable Level Controller C 16 FIGURE 3 4 continued 3095 1021A03A ...