4-9
Level Controller Configuration
Additional Options
The following options are
not
required for Level Controller operation.
Setpoint Tracking
When enabled and in manual mode, setpoint tracking automatically
changes the setpoint to the measured level value. This option is valid in
manual (MAN) mode only.
For example, assume that the target setpoint is set to 90 inches when the
controller is switched from automatic to manual mode. At the conclusion
of manual mode activities, the actual liquid level is now 82 inches.
If setpoint tracking is ON, the new target setpoint will automatically
change to 82 inches when the operator switches back to automatic mode.
Factory Default:
Tracking Disabled
Valid Options:
Tracking Disabled, Tracking Enabled
Setpoint Rate Limit
Setpoint rate limit defines the maximum ramp rate at which changes in
the setpoint are acted on. For example, assume that the setpoint rate
limit is set to 5 inches per second. When an operator changes the
setpoint from 65 to 85 inches, it will take the controller 4 seconds to
ramp to the new setpoint (20 inches
4
5 inches per second = 4 seconds).
Setting this variable to 0.0 disables setpoint rate limiting.
Factory Default:
0.0 level units per second
Valid Range:
> 0.0 level units per second
HART Comm.
6, 2, 2, 6
HART Comm.
6, 2, 2, 3
Summary of Contents for 3095
Page 2: ......
Page 4: ......
Page 8: ...viii ...
Page 10: ...Rosemount Model 3095 Multivariable Level Controller 1 2 ...
Page 42: ...Rosemount Model 3095 Multivariable Level Controller 3 10 ...
Page 74: ...Rosemount Model 3095 Multivariable Level Controller 5 18 ...
Page 98: ...Rosemount Model 3095 Multivariable Level Controller B 4 ...
Page 101: ...C 3 Approval Drawings FIGURE 3 1 continued 3095 1025A02A ...
Page 102: ...Rosemount Model 3095 Multivariable Level Controller C 4 FIGURE 3 1 continued 3095 1025A03A ...
Page 103: ...C 5 Approval Drawings FIGURE 3 2 Index of I S F M for 3095 3095 1020A01A ...
Page 104: ...Rosemount Model 3095 Multivariable Level Controller C 6 FIGURE 3 2 continued 3095 1020A02A ...
Page 105: ...C 7 Approval Drawings FIGURE 3 2 continued 3095 1020A03A ...
Page 106: ...Rosemount Model 3095 Multivariable Level Controller C 8 FIGURE 3 2 continued 3095 1020A04A ...
Page 107: ...C 9 Approval Drawings FIGURE 3 2 continued 3095 1020A05A ...
Page 108: ...Rosemount Model 3095 Multivariable Level Controller C 10 FIGURE 3 2 continued 3095 1020A06A ...
Page 110: ...Rosemount Model 3095 Multivariable Level Controller C 12 FIGURE 3 3 continued 3095 1024A02A ...
Page 111: ...C 13 Approval Drawings FIGURE 3 3 continued 3095 1024A03A ...
Page 113: ...C 15 Approval Drawings FIGURE 3 4 continued 3095 1021A02A ...
Page 114: ...Rosemount Model 3095 Multivariable Level Controller C 16 FIGURE 3 4 continued 3095 1021A03A ...