5-3
Troubleshooting and Maintenance
Interpreting Level
Controller Alarms and
Error Conditions
If an alarm or error condition exists in the Level Controller, it will be
displayed when the next Model 275 next communicates with the device.
Table 5-2 explains critical alarms, Table 5-3 lists overrange conditions,
and Table 5-4 identifies sensor limits.
Critical Alarms
Critical alarms are the highest priority Level Controller alarms, and
typically indicate an error that prevents accurate sensor or flow
measurements. Regardless of which of these alarms occur, the analog
output and the digital output respond as indicated in Table 5-2.
TABLE 5-2. Critical Alarms.
Alarm text as displayed in
Diagnostics, Error Info
Corrective Action
Output Board EEPROM Not Initialized
Output Board EEPROM Burn Failure
The output electronics has not been properly initialized at the factory. Replace the output electronics
board as described on page 5-11.
Contact your Field Service Center.
Sensor Hardware is Incompatible
The sensor electronics has undergone a component or software failure. Replace the sensor module
as described on page 5-11.
Contact your Field Service Center.
Sensor Brd EEPROM Not Initialized
The sensor electronics has undergone a component or software failure. Replace the sensor module
as described on page 5-11.
Contact your Field Service Center.
Sensor Module is Not Updating
The 10-pin ribbon cable may be disconnected, or the device electronics may have undergone a
component or software failure.
Contact your Field Service Center.
Sensor Module is Not Responding
The 10-pin ribbon cable may be disconnected, or the device electronics may have undergone a
component or software failure.
Contact your Field Service Center.
Static Pressure Sensor is Shorted
The sensor module has undergone a component or software failure. Replace the sensor module as
described on page 5-11.
Contact your Field Service Center.
RAM Failure
Issue a master reset to the device.
Device Self Test Failed
The output electronics has undergone a component or software failure. Replace the output
electronics board as described on page 5-11.
Static Pressure Sensor is Open
This display means that the device absolute pressure reading exceeds its sensor limits. There are two
possible causes. Either the device is overpressured, or it has a sensor malfunction. Check the
pressure input to the device. If an overpressure condition exists, correct it. If not, replace the sensor
module as described on page 5-11.
Process Temp Sensor is Disconnected
Check the device RTD connector and RTD screw terminals to ensure the RTD cable is pr operly
connected. For controller installations not using the RTD option, make certain the RTD option is set
to “Not Installed.”
Summary of Contents for 3095
Page 2: ......
Page 4: ......
Page 8: ...viii ...
Page 10: ...Rosemount Model 3095 Multivariable Level Controller 1 2 ...
Page 42: ...Rosemount Model 3095 Multivariable Level Controller 3 10 ...
Page 74: ...Rosemount Model 3095 Multivariable Level Controller 5 18 ...
Page 98: ...Rosemount Model 3095 Multivariable Level Controller B 4 ...
Page 101: ...C 3 Approval Drawings FIGURE 3 1 continued 3095 1025A02A ...
Page 102: ...Rosemount Model 3095 Multivariable Level Controller C 4 FIGURE 3 1 continued 3095 1025A03A ...
Page 103: ...C 5 Approval Drawings FIGURE 3 2 Index of I S F M for 3095 3095 1020A01A ...
Page 104: ...Rosemount Model 3095 Multivariable Level Controller C 6 FIGURE 3 2 continued 3095 1020A02A ...
Page 105: ...C 7 Approval Drawings FIGURE 3 2 continued 3095 1020A03A ...
Page 106: ...Rosemount Model 3095 Multivariable Level Controller C 8 FIGURE 3 2 continued 3095 1020A04A ...
Page 107: ...C 9 Approval Drawings FIGURE 3 2 continued 3095 1020A05A ...
Page 108: ...Rosemount Model 3095 Multivariable Level Controller C 10 FIGURE 3 2 continued 3095 1020A06A ...
Page 110: ...Rosemount Model 3095 Multivariable Level Controller C 12 FIGURE 3 3 continued 3095 1024A02A ...
Page 111: ...C 13 Approval Drawings FIGURE 3 3 continued 3095 1024A03A ...
Page 113: ...C 15 Approval Drawings FIGURE 3 4 continued 3095 1021A02A ...
Page 114: ...Rosemount Model 3095 Multivariable Level Controller C 16 FIGURE 3 4 continued 3095 1021A03A ...