Double Sheet Detector R1000 series E20
with integrated fieldbus interface
B0046191 / Rev. 1.12
System description
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
37
In addition to the selection by sensor number (see “11.3 System Configuration - number of
sensors"), the following sequences for the selection are available:
Sequence
Sensor 1 + sensor 2
Sensor 1 + sensor 3
Sensor 2 + sensor 3
Sensor 1 + sensor 2 + sensor 3
Sensor 1 + sensor 4
Sensor 2 + sensor 4
Sensor 3 + sensor 4
Sensor 1 + sensor 2 + sensor 4
Sensor 1 + sensor 3 + sensor 4
Sensor 2 + sensor 3 + sensor 4
Sensor 1 + sensor 2 + sensor 3 + sensor 4
Note
If all four sensors are activated, each possible sequence with only
2 or 3 sensors can be selected. On the other hand the sequences
for example for the sensor number 4 cannot be selected, if only 3
sensors are activated.
The following rule applies: The highest sensor number in the
sequence determines the minimum number of activated sensors.
Note
The sequence is a program parameter, therefore methods a) and
c) can form a practical combination, for example, two stacks of
sheet for instance left and right blanks with different thicknesses
can thus be checked for double sheet.
Pos: 27 /Kapitelübersicht/03. Montage @ 0\mod_1121421173015_501.docx @ 508 @ 1 @ 1
1.8 mm
(.07 in.)
2
3
4
1
Start
Start
1.0 mm
(.04 in.)
1.8 mm
(.07 in.)
Program
Thickness
Sensor
1
1.0 mm
1, 2
2
1.8 mm
3, 4
PLC
1. Select program 1
2. Measuring program 1
3. Analysis result of program 1
4. Select program 2
5. Measuring program 2
6. Analysis result of program 2