6.5
External I/O control
The system is normally controlled via the process channel. The exception is the signal
"Measurement start", which, for fast procedures, can also be controlled via the optocoupler inputs
(IN). A mixed operation is also possible. The control cannot, however, be made simultaneously by
both signal sources.
The “Measurement start“ signals can be initiated via the process channel or the opto couplers.
Simultaneous initiation is not possible. That means that the initiation of measurement start is not
accepted by opto couplers, if measurement start of the process channel is active or not processed.
The same applies to the other way.
optocoupler inputs
Signal Meaning
Notes
IN0
Measurement start input 1
Optocoupler input 1
24 V active
IN1
Measurement start input 2
Optocoupler input 2
24 V active
IN2
Measurement start input 3
Optocoupler input 3
24 V active
The “Measurement start“ inputs are linked in different combinations via AND. The following
configuration can be selected in the control unit:
• IN0
•
IN0 and IN1
•
IN0 and IN1 and IN2
In addition the signals 0-, 1-, 2-sheet, ENABLE and warning are available for further processing via
optocoupler (OUT).
optocoupler ouputs
Signal Meaning
Notes
OUT0
Output 0-sheet
1st Optocoupler output
standard 0 V active (selection in the control unit
configuration)
OUT1
Output 1-sheet
2nd Optocoupler output
standard 0 V active (selection in the control unit
configuration)
OUT2
Output 2-sheet
3rd Optocoupler output
standard 0 V active (selection in the control unit
configuration)
OUT3
Output ENABLE
4th Optocoupler output
standard 24 V active (cannot be selected for safety reasons)
OUT4
Warning
5th Optocoupler output
standard 0 V active (cannot be selected for safety reasons)