Manual
Double Sheet Detector R1000 series E20
with integrated fieldbus interface
Communication with the PLC
B0046191 / Rev. 1.12
104
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
6.6.6
CPS file for CC-Link
The CSP file contains the specific configuration data of the device. The data must be known to the
controller.
The manufacturers of the controller supply the tools for the integration of the CSP file into the
network. Roland Electronic does not supply such tools, because they have to be compatible with
the interface design of the controller.
The CSP file is supplied on a CD or can be downloaded from the Roland homepage.
Three „occupied Stations“ with 36 Byte are used. 12 Byte are Bit Data Area and 24 Byte Word Data
Area.
Link Input (Roland R1000 => PLC)
W0 W1 W2 W3 W4
W5
W6 W7 W8 W9 W10 W11 W12 W13 W14 W15 W16 W17
Bit Data area
word 0 to 4 (Byte 0-9)
System area
word 5
Word Data area
word 0 to 3
Word Data area
word 4 to 11
not used
Bit 3 =
Remote
Ready *1)
Roland I20
Parameter channel
(see Chapter 6.2)
Roland I20 Process channel (see Chapter 6.2)
Link Output (PLC => Roland R1000)
W0 W1 W2 W3 W4
W5
W6 W7 W8 W9 W10 W11 W12 W13 W14 W15 W16 W17
Bit Data area
word 0 to 4 (Byte 0-9)
System area
word 5
Word Data area
word 0 to 3
Word Data area
word 4 to 11
not used
not used
Roland I20
Parameter channel
(see Chapter 6.2)
Roland I20 Process channel (see Chapter 6.2)
*1) Remote Ready: after Roland R1000 is ready for Data exchange the signal Remote READY is
set. If Remote READY is off the Data are not valid.