Rockwell Automation Publication 2080-UM002L-EN-E - November 2021
79
Chapter 7 Motion Control
2. Write your motion program through the Connected Components
Workbench software
For instructions on how to use the Micro800 motion control feature, see
the quickstart instructions, Use the Motion Control Feature on Micro800
Controllers, publication
3. Wire the Controller
a. For fixed and configurable inputs/outputs, see
.
b. See
Sample Motion Wiring Configuration on 2080-LC30-xxQVB /
2080-LC50-xxQVB / 2080-LC70-xxQVB on page 81
The next sections provide a more detailed description of the motion
components. You can also see the Connected Components Workbench Online
Help for more information about each motion function block and their
variable inputs and outputs.
Input and Output Signals
Multiple input/output control signals are required for each motion axis, as
described in the next tables. PTO Pulse and PTO Direction are required for an
axis. The rest of the input/outputs can be disabled and reused as regular I/O.
These I/O can be configured through the axis configuration feature in
Connected Components Workbench. Any outputs assigned for motion should
not be controlled in the user program.
See
Motion Axis Configuration in Connected Components Workbench on
Fixed PTO Input/Output
Motion Signals
PTO0 (EM_00)
PTO1 (EM_01)
PTO2 (EM_02)
Logical Name in
Software
Name on
Terminal Block
Logical Name in
Software
Name on
Terminal
Block
Logical Name in
Software
Name on Terminal
Block
PTO pulse
_IO_EM_DO_00
O-00
_IO_EM_DO_01
O-01
IO_EM_DO_02
O-02
PTO direction
_IO_EM_DO_03
O-03
_IO_EM_DO_04
O-04
IO_EM_DO_05
O-05
Lower (Negative) Limit switch
_IO_EM_DI_00
I-00
_IO_EM_DI_04
I-04
IO_EM_DI_08
I-08
Upper (Positive) Limit switch
_IO_EM_DI_01
I-01
_IO_EM_DI_05
I-05
IO_EM_DI_09
I-09
Absolute Home switch
_IO_EM_DI_02
I-02
_IO_EM_DI_06
I-06
IO_EM_DI_10
I-10
Touch Probe Input switch
_IO_EM_DI_03
I-03
_IO_EM_DI_07
I-07
IO_EM_DI_11
I-11
Configurable input/output
Motion Signals
Input/Output
Notes
Servo/Drive On
OUTPUT
Can be configured as any embedded output.
Servo/Drive Ready
INPUT
Can be configured as any embedded input.
In-Position signal (from
Servo/motor)
INPUT
Can be configured as any embedded input.
Home Marker
INPUT
Can be configured as any embedded input, from input 0...15.