Rockwell Automation Publication 2080-UM002L-EN-E - November 2021
199
Appendix A Specifications
Input Specifications — Micro850 48-point Controllers
Attribute
2080-LC50-48AWB
2080-LC50-48QWB, 2080-LC50-48QVB, 2080-LC50-48QBB
120V AC Input
High-Speed DC Input (Inputs 0…11)
Standard DC Input (Inputs 12 and higher)
Number of Inputs
28
12
16
Input group to backplane isolation
Verified by the following dielectric tests:
1950V AC for 2 s
150V working voltage (IEC Class 2 reinforced
insulation)
Verified by the following dielectric tests: 720V DC for 2 s
50V DC working voltage (IEC Class 2 reinforced insulation)
Voltage category
110V AC
24V DC sink/source
Operating voltage range
132V, 60 Hz AC max
16.8…26.4V DC @ 65 °C (149 °F)
16.8…30.0V DC @ 30 °C (86 °F)
10…26.4V DC @ 65 °C (149 °F)
10…30.0V DC @ 30 °C (86 °F)
Off-state voltage, max
20V AC
5V DC
Off-state current, max
1.5 mA
1.5 mA
On-state current, min
5 mA @ 79V AC
5.0 mA @ 16.8V DC
1.8 mA @ 10V DC
On-state current, nom
12 mA @ 120V AC
7.6 mA @ 24V DC
6.15 mA @ 24V DC
On-state current, max
16 mA @ 132V AC
12.0 mA @ 30V DC
Nominal impedance
12 k
Ω
@ 50 Hz
10 k
Ω
@ 60 Hz
3 k
Ω
3.74 k
Ω
IEC input compatibility
Type 3
Inrush current, max
250 mA @ 120V AC
–
Input frequency, max
63 Hz
–
Isolated AC Inputs — Micro850 48-point Controllers
Attribute
2080-LC50-48QWB, 2080-LC50-48QVB, 2080-LC50-48QBB
(Inputs 0…11)
On-state voltage, nom
12/24V AC @ 50/60 Hz
Off-state voltage, min
4V AC @ 50/60Hz
Operating frequency, nom
50/60 Hz
Output Specifications — Micro850 48-point Controllers
Attribute
2080-LC50-48AWB, 2080-LC50-48QWB
2080-LC50-48QVB, 2080-LC50-48QBB
Relay Output
Hi-Speed Output (Outputs 0…3)
Standard Output (Outputs 4 and higher)
Number of outputs
20
4
16
Output voltage, min
5V DC, 5V AC
10.8V DC
10V DC
Output voltage, max
125V DC, 265V AC
26.4V DC
26.4V DC
Load current, min
10 mA
Load current,
continuous, max
2.0 A
100 mA (high-speed operation)
1.0 A @ 30 °C
0.3 A @ 65 °C (standard operation)
1.0 A @ 30 °C
0.3 A @ 65 °C (standard operation)
Surge current, per point
See
Relay Contacts Ratings — Micro850 48-
4.0 A for 10 ms every 1 s @ 30 °C; every 2 s @ 65 °C
(1)
Current, per common, max
5 A
–
–
Turn on time/
Turn off time, max
10 ms
2.5 µs
ON: 0.1 ms
OFF: 1 ms
(1) Applies for general-purpose operation only. Does not apply for high-speed operation