200
Rockwell Automation Publication 2080-UM002L-EN-E - November 2021
Appendix A Specifications
For the Micro850 controller relay chart, see
Micro850, and Micro870 Controllers on page 206
.
Environmental Specifications
Relay Contacts Ratings — Micro850 48-point Controllers
Maximum Volts
Amperes
Amperes Continuous
Volt-Amperes
Make
Break
Make
Break
120V AC
15 A
1.5 A
2.0 A
1800V A
180V A
240V AC
7.5 A
0.75 A
24V DC
1.0 A
1.0 A
28V A
125V DC
0.22 A
Environmental Specifications — Micro850 Controllers
Attribute
Value
Temperature, operating
IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock):
-20…+65 °C (-4…+149 °F)
Temperature, surrounding air, max
65 °C (149 °F)
Temperature, nonoperating
IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold),
IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat),
IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock):
-40…+85 °C (-40…+185 °F)
Relative humidity
IEC 60068-2-30 (Test Db, Unpackaged Damp Heat):
5…95% non-condensing
Vibration
IEC 60068-2-6 (Test Fc, Operating):
2 g @ 10…500 Hz
Shock, operating
IEC 60068-2-27 (Test Ea, Unpackaged Shock):
25 g
Shock, nonoperating
IEC 60068-2-27 (Test Ea, Unpackaged Shock):
DIN mount: 25 g
PANEL mount: 35 g
Emissions
IEC 61000-6-4
ESD immunity
IEC 61000-4-2:
6 kV contact discharges
8 kV air discharges
Radiated RF immunity
IEC 61000-4-3:
10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz
10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz
10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz
10V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz
EFT/B immunity
IEC 61000-4-4:
±2 kV @ 5 kHz on power ports
±2 kV @ 5 kHz on signal ports
±1 kV @ 5 kHz on communication ports
Surge transient immunity
IEC 61000-4-5:
±1 kV line-line(DM) and ±2 kV line-earth(CM) on signal ports
±1 kV line-earth(CM) on communication ports
Conducted RF immunity
IEC 61000-4-6:
10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz