Chapter 8 Use the High-Speed Counter and Programmable Limit Switch
can be used in the control program to identify that the low preset condition
caused the HSC interrupt. If the control program needs to perform any
specific control action based on the low preset, this bit would be used as
conditional logic.
This bit can be cleared (0) by the control program and is also be cleared by the
HSC sub-system whenever these conditions are detected:
•
High Preset Interrupt occurs
•
Underflow Interrupt occurs
•
Overflow Interrupt occurs
When the HSC is in Counting mode, and PLS is enabled, this parameter
indicates which PLS element is used for the current HSC configuration.
The Error Codes detected by the HSC sub-system are displayed in this word.
Errors include:
Writing to this element is not recommended except for clearing existing errors
and to capture new HSC errors.
HSCSTS.Accumulator contains the number of counts detected by the HSC
sub-system. If either mode 0 or mode 1 is configured, the accumulator is reset
to 0 when a high preset is reached or when an overflow condition is detected.
Programmable Limit Switch Position (HSCSTS.PLSPosition)
Description
Data Format
HSC Modes
(1)
(1) For Mode descriptions, see
HSC Mode (HSCAPP.HSCMode) on page 127
.
User Program Access
HSCSTS.PLSPosition
Word (INT)
0…9
read only
Error Code (HSCSTS.ErrorCode)
Description
Data Format
HSC Modes
(1)
(1) For Mode descriptions, see
HSC Mode (HSCAPP.HSCMode) on page 127
.
User Program Access
HSCSTS.ErrorCode
Word (INT)
0…9
read only
Error Code Sub-element
HSC Counting Error
Code
Error Description
Bit 15…8 (high byte)
0…255
The non-zero value for high byte indicates that the HSC
error is due to PLS data setting. The value of high byte
indicates which element of PLS data triggers the error.
Bit 7…0 (low byte)
0x00
No error
0x01
Invalid HSC counting mode
0x02
Invalid High preset
0x03
Invalid overflow
0x04
Invalid underflow
0x05
No PLS data
Accumulator (HSCSTS.Accumulator)
Description
Data Format
User Program Access
HSCSTS.Accumulator
long word (32-bit INT)
read only
High Preset (HSCSTS.HP)
Description
Data Format
User Program Access
HSCSTS.HP
long word (32-bit INT)
read only