188
Rockwell Automation Publication 2080-UM002L-EN-E - November 2021
Appendix A Specifications
Output circuit type
Relay
12/24V DC sink transistor (standard and
high-speed)
Event input interrupt support
Yes
Power consumption, max
5 W – without plug-in modules
7.88 W – with plug-in modules
Power supply voltage range
20.4…26.4V DC Class 2
I/O rating
Input:
120V AC, 16 mA
Output:
2 A, 240V AC, general use
Input:
24V DC, 8.8 mA
Output:
2 A, 240V AC, general use
Input:
24V DC, 8.8 mA
Output:
24V DC, 1 A per point
(Surrounding air temperature 30 °C)
24V DC, 0.3 A per point
(Surrounding air temperature 65 °C)
Isolation voltage
250V (continuous), Reinforced Insulation
Type, Outputs to Aux and Network, Inputs to
Outputs
Type tested for 60 s @ 3250V DC I/O to Aux
and Network, Inputs to Outputs
250V (continuous), Reinforced Insulation
Type, Outputs to Aux and Network, Inputs to
Outputs
Type tested for 60 s @ 720V DC, Inputs to
Aux and Network, 3250V DC Outputs to Aux
and Network, Inputs to Outputs
50V (continuous), Reinforced Insulation Type,
I/O to Aux and Network, Inputs to Outputs
Type tested for 60 s @ 720V DC, I/O to Aux
and Network, Inputs to Outputs
Pilot duty rating
C300, R150
–
Insulation stripping length
7 mm (0.28 in.)
Enclosure type rating
Meets IP20
North American temp code
T4
(1) Use this Conductor Category information for planning conductor routing. See Industrial Automation Wiring and Grounding Guidelines, publication
.
General Specifications — Micro830 16-point Controllers (Continued)
Attribute
2080-LC30-16AWB
2080-LC30-16QWB
2080-LC30-16QVB
Inputs — Micro830 16-point Controllers
Attribute
2080-LC30-16AWB
2080-LC30-16QVB, 2080-LC30-16QWB
120V AC Input
High-Speed DC Input (Inputs 0…3)
Standard DC Input (Inputs 4…9)
Number of Inputs
10
4
6
Input group to backplane
isolation
Verified by the following dielectric tests: 1,400V AC for 2 s
132V working voltage (IEC Class 2 reinforced insulation)
Verified by the following dielectric tests: 1,414V DC for 2 s
75V DC working voltage (IEC Class 2 reinforced insulation)
Voltage category
110V AC
24V DC sink/source
On-state voltage range
79…132V AC
47…63 Hz
16.8…26.4V DC
10…26.4V DC
Off-state voltage, max
20V AC
5V DC
Off-state current, max
1.5 mA
On-state current, min
5 mA @ 79V AC
5.0 mA @ 16.8V DC
1.8 mA @ 10V DC
On-state current, nom
12 mA @ 120V AC
7.66 mA @ 24V
6.15 mA @ 24V
On-state current, max
16 mA @ 132V AC
12.0 mA @ 30V DC
Nominal impedance
12 k
Ω
@ 50 Hz
10 k
Ω
@ 60 Hz
3 k
Ω
3.74 k
Ω
Inrush current, max
250 mA @ 120V AC
—
Turn on time/
Turn off time, max
(without filtering)
ON: 1 ms
OFF: 8 ms
ON: 3.2 µs
OFF: 0.6 µs
ON: 33 µs…0.1 ms
OFF: 22 µs…0.02 ms
IEC input compatibility
Type 3
AC input filter setting
8 ms for all embedded inputs
(In Connected Components Workbench software, go to the Embedded I/O configuration window to reconfigure the filter setting for each input
group)