126
Rockwell Automation Publication 2080-UM002L-EN-E - November 2021
Chapter 8 Use the High-Speed Counter and Programmable Limit Switch
This bit enables and disables the HSC Programmable Limit Switch (PLS)
function.
When the PLS function is enabled, the setting in
•
HSCAPP.HpSetting
•
HSCAPP.LpSetting
•
HSCAPP.HPOutput
•
HSCAPP.LPOutput
are superseded by corresponding data values from PLS data. See
Programmable Limit Switch (PLS) Function on page 142
for more information.
lists the definition for HSCID.
HSC1, HSC3, and HSC5 support mode 0, 2, 4, 6, and 8 only, and HSC0, HSC2,
and HSC4 support all counting modes.
PLS Enable (HSCAPP.PLSEnable)
Description
Data Format
User Program Access
PLSEnable
bit
read/write
HSCID (HSCAPP.HSCID)
Description
Data Format
User Program Access
HSCID
Word (UINT)
read/write
Table 22 - HSCID Definition
Bits
Description
15…13
HSC Module Type:
0x00: Embedded
0x01: Expansion (not yet implemented)
0x02: Plug-in module
12…8
Module Slot ID:
0x00: Embedded
0x01…0x1F: Expansion (not yet implemented)
0x01…0x05: Plug-in module
7…0
Module internal HSC ID:
0x00-0x0F: Embedded
0x00-0x07: Expansion (not yet implemented)
0x00-0x07: Plug-in module