Rockwell Automation Publication 2080-UM002L-EN-E - November 2021
197
Appendix A Specifications
For the Micro850 controller relay chart, see
Micro850, and Micro870 Controllers on page 206
.
Input frequency, min
47 Hz
Input frequency, nom
50/60 Hz
Input frequency, max
63 Hz
Off-state voltage, max
20V AC @ 120V AC
Off-state current, max
2.5 mA @ 120V AC
Inrush current. max
250 mA @ 120V AC
Inrush delay time constant max
22 ms
IEC input compatibility
Type 3
Isolated AC Inputs — Micro850 24-point Controllers
Attribute
2080-LC50-24QWB, 2080-LC50-24QVB, 2080-LC50-24QBB
(Inputs 0…7)
On-state voltage, nom
12/24V AC @ 50/60 Hz
Off-state voltage, min
4V AC @ 50/60Hz
Operating frequency, nom
50/60 Hz
AC Input Specifications — Micro850 24-point Controllers (Continued)
Attribute
2080-LC50-24AWB
Output Specifications — Micro850 24-point Controllers
Attribute
2080-LC50-24QWB 2080-LC50-24AWB
2080-LC50-24QVB, 2080-LC50-24QBB
Relay Output
Hi-Speed Output (Outputs 0...1)
Standard Output (Outputs 2 and higher)
Number of outputs
10
2
8
Output voltage, min
5V DC, 5V AC
10.8V DC
10V DC
Output voltage, max
125V DC, 265V AC
26.4V DC
26.4V DC
Load current, min
10 mA
Load current,
continuous, max
2.0 A
100 mA (high-speed operation)
1.0 A @ 30 °C
0.3 A @ 65 °C (standard operation)
1.0 A @ 30 °C
0.3 A @ 65 °C (standard operation)
Surge current, per point
See
Relay Contacts Ratings — Micro850 24-
4.0 A for 10 ms every 1 s @ 30 °C; every 2 s @ 65 °C
(1)
Current, per common, max
5 A
–
–
Turn on time/
Turn off time, max
10 ms
2.5 µs
0.1 ms
1 ms
(1) Applies for general-purpose operation only; does not apply for high-speed operation.
Relay Contacts Ratings — Micro850 24-point Controllers
Maximum Volts
Amperes
Amperes Continuous
Volt-Amperes
Make
Break
Make
Break
120V AC
15 A
1.5 A
2.0 A
1800V A
180V A
240V AC
7.5 A
0.75 A
24V DC
1.0 A
1.0 A
28V A
125V DC
0.22 A