124
Rockwell Automation Publication 2080-UM002L-EN-E - November 2021
Chapter 8 Use the High-Speed Counter and Programmable Limit Switch
The following tables show the input wiring mapping for the different
Micro830, Micro850, and Micro870 controllers.
HSC3
A/C
B/D
HSC4
A/C
B/D
Reset Hold
HSC5
A/C
B/D
Table 18 - HSC Input Wiring Mapping (Continued)
Embedded Input
0
01
02
03
04
05
06
07
08
09
10
11
Table 19 - Micro830 10 and 16-point Controller HSC Input Wiring Mapping
Modes of Operation
Input 0 (HSC0)
Input 2 (HSC1)
Input 1 (HSC0)
Input 3 (HSC1)
Input 2 (HSC0)
Input 3 (HSC0)
Mode Value in
User Program
(HSCAppData.HSCMode)
Counter with Internal Direction
(mode 1a)
Count Up
Not Used
0
Counter with Internal Direction,
External Reset and Hold (mode 1b)
Count Up
Not Used
Reset
Hold
1
Counter with External Direction
(mode 2a)
Count Up/Down
Direction
Not Used
2
Counter with External Direction,
Reset, and Hold (mode 2b)
Count
Direction
Reset
Hold
3
Two Input Counter (mode 3a)
Count Up
Count Down
Not Used
4
Two Input Counter with External
Reset and Hold (mode 3b)
Count Up
Count Down
Reset
Hold
5
Quadrature Counter (mode 4a)
A Type input
B Type input
Not Used
6
Quadrature Counter with External
Reset and Hold (mode 4b)
A Type input
B Type input
Z Type Reset
Hold
7
Quadrature X4 Counter
(mode 5a)
A Type input
B Type input
Not Used
8
Quadrature X4 Counter with External
Reset and Hold
A Type input
B Type input
Z Type Reset
Hold
9
Table 20 - Micro830/Micro850/Micro870 24-point Controller HSC Input Wiring Mapping
Modes of Operation
Input 0 (HSC0)
Input 2 (HSC1)
Input 4 (HSC2)
Input 6 (HSC3)
Input 1 (HSC0)
Input 3 (HSC1)
Input 5 (HSC2)
Input 7 (HSC3)
Input 2 (HSC0)
Input 6 (HSC2)
Input 3 (HSC0)
Input 7 (HSC2)
Mode Value in User
Program
Counter with Internal Direction
(mode 1a)
Count Up
Not Used
0
Counter with Internal Direction,
External Reset and Hold (mode 1b)
Count Up
Not Used
Reset
Hold
1
Counter with External Direction
(mode 2a)
Count Up/Down
Direction
Not Used
2
Counter with External Direction,
Reset, and Hold (mode 2b)
Count Up/Down
Direction
Reset
Hold
3
Two Input Counter (mode 3a)
Count Up
Count Down
Not Used
4
Two Input Counter with External
Reset and Hold (mode 3b)
Count Up
Count Down
Reset
Hold
5
Quadrature Counter (mode 4a)
A Type input
B Type input
Not Used
6